Automation Networks ANC-120e Handmatig - Pagina 4
Blader online of download pdf Handmatig voor {categorie_naam} Automation Networks ANC-120e. Automation Networks ANC-120e 4 pagina's. Compact usb to data highway plus adapter
Ook voor Automation Networks ANC-120e: Gebruikershandleiding (18 pagina's)
ANC-120e
USB to DH+ Adapter
Appendix
ANC-120e DH+ connection
There are 2 ways to connect to the DH+ network.
Connect to Processor's 3-pin connector: Daisy chain a cable from the last DH+
-
node to the connector of ANC-120e. (Cable shield is not required for ANC-
120e). Polarity is irrelevant, as it is auto-detected by ANC-120e
Connect to DH+ Programming Terminal on processor by using the ANC-120e
-
Mini-Din Programming Cable
Connect the DH+ cable to ANC-120e and then connect to a free USB port on your
computer.
When the unit turns on, the USB LED blinks several times.
Note: if AUTO Baud rate and AUTO DH+ Node options are active in ANC-120e,
the device will automatically configure the correct DH+ network speed and find a
free DH+ node number to use as its own address. So you don't need any
configuration to start programming DH+ processor.
The ANC-120e DH+ side LED blinks every 3 seconds if it is associated with the DH+
network and nothing is being transmitted on the DH+ link. When DH+ data exchange
takes place, the LED will indicate this by blinking rapidly upon transmitting/receiving a
valid DH+ packet. DH+ LED will remain off if the DH+ network is not connected or
there are no devices on the connected network.
About RSWho window and AutoBrowse option
RSLinx "Autobrowse" option is good to initially discover all active nodes on a particular
DH+ network quickly and easily, however, because of the extra traffic this feature
generates, it is recommended to have the "Autobrowse" checkbox unchecked in the
production environment.
For more information about settings and other options, please refer to ANC-120e User
Manual.
4