b. Monitor the motor current. Since current is proportional to torque, check your nameplate for
the rated motor current to determine to desired torque limit. Example- If your drive is rated
at 10 amps, and you want to limit the torque (150% of 10 amperes is 15 amperes), start the
drive and note the maximum current on the ac ammeter during acceleration. If the current is
less than 150% of rated motor torque, increase the Torque Limit setting R19 CW. If the current
rating is too high, decrease the Torque Limit setting CCW. Stop the unit and repeat the Start
Up. Check on the ac ammeter during acceleration. If the motor current during acceleration
never reaches 150% of rated motor current, increase the load and repeat current monitoring.
c. When the clutch is being torque limited, decrease the setting of the Torque Damping
potentiometer R18 CCW until instability (hunting) develops. Then increase the setting CW
until stability is attained. Recheck the Torque Limit setting as described in step 11b and
readjust if necessary.
12.
Torque Limit PCB 15-444-2 (If normal load cannot be applied)
a. Apply a load to the motor and note the motor current (IR) (a load of 50% of full load or more
is desirable)
b. Check the motor nameplate for full load current (IF) of the motor.
c. Connect a voltmeter across terminals 1 and 2 measure the voltage (VR) at a motor current of
IR.
d. Calculate what the voltage would be across terminals 1 and 2 at full load:
VF = Current xfmr output voltage at full load
VR = Current xfmr output voltage at reduced load
IF = Motor current at full load
IR = Motor current at reduced load
e. Disconnect the leads to terminals 1 and 2 on 15-444-2 Modification board and connect a
variac.
f.
Adjust the variac for VF and adjust the Torque Limit pot until the output speed of the drive
just begins to decrease. Increasing the output of the variac slightly will cause the speed of the
drive to decrease sharply. When making this adjustment DO NOT exceed 75 volts out of the
variac.
g. Torque Limit Damping- Follow the procedure outlined in step 11c. Load must be applied, and
the circuit must be limiting torque to make this adjustment.