General Specifications
Operating Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
> 10MΩ @ 500VDC
Heat Dissipation
6.4 W
Enclosure Type
Open Equipment
Module Keying to Backplane
Electronic
Module Location
Any I/O slot in a Productivity2000 System
Use ZIPLink Wiring System ONLY. See "Wiring Options"
Field Wiring
on page 5. Must use copper conductors 75ºC or
equivalent.
See the "EU Directive" topic in the Productivity2000
EU Directive
Help File. Information can also be obtained at:
www.productivity2000.com
Connector Type
24-Pin Molex Style 43025-2400
Weight
90g (3.2 oz)
UL 61010-1 and UL 61010-2-201 File E139594, Canada
and USA
Agency Approvals
CE (EN 61131-2 EMC, EN 61010-1 and EN 61010-2-
201 Safety)*
*Meets EMC and Safety requirements. See the D.O.C. for details.
2
www.productivity2000.com
Output Specifications
Output Channels
16
Module Signal Output Range
±10VDC
Output Signal Resolution
16-bit
Resolution Value of LSB
±10VDC = 305μV/count
(least significant bit)
1 LSB = 1 count
Data Range
-32768 to 32767 counts
Output Type (sourcing/sinking)
Voltage: 10mA max current
Output Value in Fault Mode
0V
Load Impedance
≥1000Ω
Maximum Capacitive Load
0.01μF maximum
Allowed Load Type
Grounded
0.1% of range
Maximum Inaccuracy
(including temperature drift)
Maximum Full Scale Calibration
±0.025% of range maximum
Error (not including offset error)
Maximum Offset Calibration Error
±0.025% of range maximum
±25ppm/°C max full scale calibration change
Accuracy vs. Temperature
(±0.0025% of range/°C)
Max Crosstalk
-96dB, 1 LSB
±16 LSB maximum (±0.025% of full scale)
Linearity Error (End to End)
Monotonic with no missing codes
Output Stability and Repeatability
±10 LSB after 10 minute warm-up (typical)
Output Ripple
0.05% of full scale
Output Setting Time
300μs max, 5μs min (full scale change)
All Channel Update Rate
3ms
Outputs current limited to 40mA typical.
Maximum Continuous Overload
Continuous overloads on multiple output
can damage the module.
Type of Output Protection
0.1μF Transient Suppressor
External DC Power Required
24VDC (-20% / +25%), 265mA
Tech Support 770-844-4200