AutomationDirect GS1 Series Gebruikershandleiding - Pagina 8
Blader online of download pdf Gebruikershandleiding voor {categorie_naam} AutomationDirect GS1 Series. AutomationDirect GS1 Series 16 pagina's.
Appendix A: Accessories
L
R
a
ine
eactoR
ppLicationS and
i
S
ac d
nput
ide of
When installed on the input side of the AC Drive, line reactors will reduce line notching, and limit current
and voltage spikes and surges from the incoming line. The line reactors will also reduce harmonic
distortion from the AC Drive onto the line. Units are installed in front of the AC Drive as shown.
Reactor
C1
B1
A1
o
S
utput
ide of
When installed on the output side of the AC Drive, line (load) reactors protect the drive from short circuits
at the load. Voltage and current waveforms from the drive are enhanced, reducing motor overheating and
noise emissions.
1.0HP
230V 3PH
Single-phase line reactors should NOT be installed on the output of the AC Drive. Use only three-
phase reactors on drive outputs, and only for three-phase motors.
If installing a line reactor on the output side of the drive, especially with motor lead lengths in
excess of 75 feet, lower the drive PWM output carrier frequency to 4kHz in order to protect the line
reactor from excess heating and possible damage.
Page A–8
c
onnectionS
Rive
C2
L3
B2
L2
1.0HP
230V 3PH
A2
L1
ac d
Rive
Reactor
T3
C1
T2
B1
T1
A1
GS1 Series AC Drives User Manual – 3rd Edition – 11/09/2018