Automationdirect.com Productivity 2000 P2-16DAL-2 Handmatig - Pagina 2

Blader online of download pdf Handmatig voor {categorie_naam} Automationdirect.com Productivity 2000 P2-16DAL-2. Automationdirect.com Productivity 2000 P2-16DAL-2 8 pagina's. Analog output

Automationdirect.com Productivity 2000 P2-16DAL-2 Handmatig

General Specifications

Surrounding Temperature
0º to 60ºC (32º to 140ºF)
Storage Temperature
-20º to 70ºC (-4º to 158ºF)
Humidity
5 to 95% (non-condensing)
Environmental Air
No corrosive gases permitted
Vibration
IEC60068-2-6 (Test Fc)
Shock
IEC60068-2-27 (Test Ea)
Field to Logic Side Isolation
1800VAC applied for 1 second
Insulation Resistance
> 10MΩ @ 500VDC
Heat Dissipation
8W
Enclosure Type
Open Equipment
UL508 File E139594, Canada & USA
Agency Approvals
CE (EN61131-2*)
Module Keying to Backplane
Electronic
Module Location
Any I/O slot in a Productivity2000 System
Use ZIPLink Wiring System ONLY. See "Wiring Options"
Field Wiring
on page 5. Must use copper conductors 75°C or
equivalent.
See the "EU Directive" topic in the Productivity Suite
EU Directive
Help File. Information can also be obtained at:
www.productivity2000.com
Terminal Type
24 Position ZIPLink Connector
Weight
100g (3.5 oz)
*Meets EMC and Safety requirements. See the D.O.C. for details.
2
www.productivity2000.com

Output Specifications

Output Channels
Module Signal Input Range
Output Signal Resolution
Resolution Value of LSB
(least significant bit)
Data Range
Output Type
Output Value in Fault Mode
Load Impedance
Maximum Capacitive Load
Allowed Load Type
Maximum Inaccuracy
Maximum Full Scale Calibration Error
Maximum Offset Calibration Error
Accuracy vs. Temperature
Max Crosstalk at DC, 50/60Hz
Linearity Error (End to End)
Output Stability and Repeatability
Output Ripple
Output Settling Time
All Channel Update Rate
Maximum Continuous Overload
Type of Output Protection
External 24VDC Power Required
Tech Support 770-844-4200
16
0-10 V
12-bit
0-10 V = 2.44 mV per count
1 LSB = 1 count
0 to 4095 counts
Voltage sourcing at 10mA max. (1 common)
0V
0.2Ω typical
0.01 µF maximum
Grounded
0.5% of range
(including temperature drift)
±0.2% of range maximum voltage
±0.2% of range maximum
±75 PPM / °C maximum full-scale calibration change
(±0.0025% of range / °C)
-72dB, 1 LSB
±4 LSB maximum, (±0.1% of full scale)
Monotonic with no missing codes
±2% LSB after 10 min. warm up period
±0.1% of full scale
300µs max., 5µs min. (full scale range)
1ms
Outputs current limited to 40mA typical;
Continuous overloads on multiple outputs can damage
the module.
0.1µF Transient Suppressor
24VDC (-20% / + 25%), 265mA