Hidro-Water KOBE WS1CI UF Gebruikers- en installatiehandleiding - Pagina 9
Blader online of download pdf Gebruikers- en installatiehandleiding voor {categorie_naam} Hidro-Water KOBE WS1CI UF. Hidro-Water KOBE WS1CI UF 19 pagina's. Water conditioning system
6.4.- Programming
Always starting from the service state, at the same time press
to enter the programming mode.
6.4.1 Inlet hardness
Introduce the hardness value of the water to be treated in PPM (mg/l CaCO3) (PPM= °F x 10)
Set the hardness using
Press
parameter
6.4.2 Outlet hardness
Hidro-Water recommends leaving a residual hardness of between 80 and 100 PPM (mg/l CaCO3).
Adjust residual hardness using
to 90 ppm
Press
parameter
You can check in point 8.5.- Residual hardness setting, in this manual, how to make the adjustment
residual hardness.
6.4.3 Forced regeneration
This is a safety measure to avoid water becoming stagnant for a prolonged period as this may
biologically contaminate the resins.
SET
Adjust days using
REGEN
Press
DAY
parameter
6.4.4 Regeneration time
By default, the programmed regeneration time is 2:00 am as it's a time when generally there won't
be any water consumption and therefore there'll be good pressure. If you want the regenerations
to be at a different time for whatever reason, programme the desired time in this parameter.
Adjust hour using
SET TIME
Confirm using
Adjust minutes using
REGEN
Confirm using
service screen. The system has been programmed.
16
MA-EN-DESCALCIFICADOR KOBE (USR) UF-3004-XX JD18V01
+
for 3 seconds
NEXT
NEXT
to confirm and move onto the next
, programme
to confirm and move onto the next
NEXT
programme 7
NEXT
to confirm and move onto the next
programme 2
NEXT
programme 00
And we'll be put back to the
NEXT
7.- INSTALLATION CHECK LIST
Installation
Description
System positioning
Hydraulic connections checked
Inlet-Outlet // Bypass connected correctly and
sealed tight
Drainage connected correctly and sealed tight
Brine connected correctly and sealed tight
Overflow connected correctly and sealed tight
Electric connection
Programming carried out
8.- START UP
Once the valve has been programmed, it's time to start up the system.
8.1.- Bleeding air
Make sure the softener's inlet and outlet valve are
closed and that the bypass is open to make sure
there's water available.
SOFTENER
SOFTENER
Position the valve in the BACKWASH position.
TIME
REMAINNING
Press
BRINE UP cycle. Wait until it is totally positioned (the motor
REGEN
MIN
stops being heard and time starts to count down).
BACKWASH
When the softener is totally positioned, press and release
BACKWASH cycle.
When it's totally positioned, unplug the transformer from the electric supply.
½ open the bypass inlet valve and let the bottle fill slowly.
You'll hear the air escaping down the drain. Keep it like this
until all of the air has been removed. You'll know as now
water is being released into the drain and it doesn't have
any bubbles.
SOFTENER
SOFTENER
If you open it too much or too fast, you can damage the system and /or lose resin.
In this position, you must listen to the air escaping slowly in the drainage line.
MA-EN-DESCALCIFICADOR KOBE (USR) UF-3004-XX JD18V01
Ok?
for 5 seconds The softener will go into the
REGEN
The softener will go into the
REGEN
17