Blader online of download pdf Installatie- en onderhoudshandleiding voor {categorie_naam} Celina Wisperkool 20 Ton. Celina Wisperkool 20 Ton 13 pagina's. Portable vertical air-conditioning and heating systems 480v

Celina Wisperkool 20 Ton Installatie- en onderhoudshandleiding

Electrical Information

All 20 ton wisperkool™ air conditioning units are
480V, 3-phase, 60 Hz.
Each unit has eight color coded cam-type electrical connections. When connecting one unit
to a power source the male cam-type connections on the top should be used. The bottom
row female cam-type connections are only to be used when connecting multiple units to one
power source and allows connecting several units in series. Either 2/0 or 4/0 electrical cable
should be used. When connecting multiple units in series do not exceed amp rating of cable
used. Exceeding amp ratings could cause permanent damage to the electrical cables.
Circuit Breaker
Maximum Over-current Protection
(MCA) – cooling with heat
Compressor
Compressor RLA
Evaporator Blower Motor
Evaporator Blower FLA
Condenser Blower Motor
Condenser Blower RLA (each-2)
Heater kW (total)
Heater Amperage (total)
Heater kW each stage
Heater Stages
EXTERNAL POWER MUST MATCH VOLTAGE RATING 480/3/60
DO NOT EXCEED AMP RATING
Yes
75 amps
33 amps
15 amps
5 hp
6.3 amps
2 hp
3.4 amps
45
60
22.5 kW
2
20 TON
480V
7