The unit may be mounted on a wall or solid ceiling using brackets supplied. It should be matched with the
appropriately sized outdoor unit; this instruction should be used in conjunction with the outdoor unit
installation instructions.
1.
Fit all kits prior to installing the unit. (Heater kit is easier to fit when unit has been mounted).
2.
Ensure that the mounting surface will support the operating weight of the unit (see table below).
3.
Mark out the mounting positions and drill holes to suit 6mm rawlbolt shields or equivalent strength
fasteners (ensure that the unit is positioned
to give sufficient access (min 0.5m) to the
electrics access side).
4.
Fix the mounting brackets to the unit in the
correct position for wall or ceiling mounting.
5.
Raise the unit into position and secure the
fixings, ensuring that it is square and level.
6.
Remove the drain tray then fit the drain stub,
nut & gasket (Fig.1). Refit the drain tray.
NITROGEN CHARGE
The unit contains a small charge of dry nitrogen, which should be discharged into the atmosphere. This is a
non-toxic, non-ozone depleting gas with no global warming potential.
PIPE CONNECTIONS
Pipework is terminated with 2 flare nuts & bonnets. Access is via the rear right hand side. Pipes exit the unit
through holes in the back panel.
INTERCONNECTING PIPEWORK (Max 15 metres)
System
CX(E)A 30 + CKA35
CX(E)A 50 + CKA35
CX(E)A 50 + CKA50
CX(E)A 70 + CKA70
CONDENSATE DRAIN
Push fit connections are widely available for the 7/8" (22mm) OD condensate drain and 3/4"(19mm) ID drain
stub adaptor. Alternatively 7/8" (22mm) bore plastic tubing may be fitted directly to the stub/adaptor with a
hose clamp. Take care not to over tighten hose clamps as this could damage the stub pipe.
CX(E)A INSTALLATION
CONTENTS
PARTS DESCRIPTION
CX(E)A PIPEWORK
Liquid/
Suction
Expansion
1/4"
1/2"
1/4"
1/2"
1/4"
1/2"
3/8"
5/8"
ACTION
Pass to the end user
Fitted by installer
Convert to ¾" drain if required
Use to hang unit
Torque (NM)
Liquid
Suction
Line
Line
17
54
17
54
17
54
34
73
7/9
Fig.1
Nut A/F (mm)
Liquid
Suction
Line
Line
17
24
17
24
17
24
22
27
55908028-03