Autonics TZN4M Handmatig - Pagina 8

Blader online of download pdf Handmatig voor {categorie_naam} Autonics TZN4M. Autonics TZN4M 17 pagina's. Dual pid control temperature controller
Ook voor Autonics TZN4M: Handmatig (4 pagina's), Gebruiksaanwijzing (2 pagina's), Handmatig (16 pagina's), Handmatig (16 pagina's), Handmatig (17 pagina's)

Autonics TZN4M Handmatig

Parameter 2 group

Run mode
If pressing
+
MD
+
3sec.
MD
※ 2
Event 1
Event 2
Input type
mode
mode
MD
MD
IN-T
EU-1
EU-2
KCaH
LBA
LBA
KCaL
SBA
SBA
JIcH
AL-0
AL-0
JIcL
AL-1
AL-1
R PR
AL-2
AL-2
ECrH
AL-3
AL-3
ECrL
AL-4
AL-4
TCcH
AL-5
AL-5
TCcL
AL-6
AL-6
S PR
NN
U TT
JPtH
JPtL
Input type: Select from 19 type
IN-T
Event 1: Select from 9 type
EU-1
DPtH
Event 2: Select from 9 type
EU-2
Alarm type: Select from 4 type
AL-T
DPtL
Auto-tuning: Selectable TUN1 or TUN2.
AtT
A--1
PID: Selectable PIDF or PIDS.
PIDT
Selectable heat-function or cool-function
O-FT
A--2
※ 1
Temperature unit: ℃ or ℉
UNIT
Set scaling high limit (include analog output)
H-SC
A--3
※ Press
( ) key and the right digit of SV display part flashes. Press
Press
( ),
( ) keys to change SV and press
※ After completing setting at each parameter, press
※ If no key touched for 60sec., it will return to RUN mode automatically.
※ 1: It may not be displayed by input type switch.
※ 2: This is displayed only for model with High/Low-limit of transmission output.
Factory defaults(Parameter 2 group)
Parameter
Factory default
IN-T
KCaH
EU-1
AL-1
EU-2
AL-2
Dual PID Auto Tuning Control
key for 3sec. at once in RUN state, it will go to parameter 2 group.
Auto-tuning
Alarm type
type
PID type
MD
MD
MD
AL-T
AtT
PIDT
AL-A
TVN1
PIdS
AL-B
TVN2
PIdF
AL-C
AL-D
Input type
Lock
MD
IN-T
LOC
OFF
key to complete the set. Press
MD
key for 3 sec. and it returns to RUN mode.
MD
Parameter
Factory default
AL-T
AL-A
AtT
TVN1
RAMP
OFF
Control
operating
Temperature
type
unit
MD
MD
MD
O-FT
UNIT
HEAT
?C
COOL
?F
※ 2
Communication
Communication
address
speed
MD
MD
MD
ADRS
BPS
01
2400
ON
4800
9600
Set scaling low limit (include analog output)
L-SC
Select decimal point position for Analog input
DOT
Set the high-limit when retransmission output is applied. (20mA)
FS-H
Set the low-limit when retransmission output is applied. (4mA)
FS-L
Able to set ON and OFF of Ramp function.
RAMP
Set communication speed
BPS
Set communication address(01 to 99)
ADRS
The data cannot be changed when the lock key is ON
LOC
( ) or
( ) key and move to the desired digit.
key again and it moves to next parameter.
MD
Parameter
Factory default
PIDT
PIdS
O-FT
HEAT
UNIT
?C
※ 1
Scaling
Scaling
Decimal
high limit
low limit
point
MD
MD
H-SC
L-SC
DOT
1300
-100
0
)0
)00
)000
※ 2
Transmission
Transmission
Ramp
output
output
function
low limit
high limit
MD
MD
RAMP
FS-L
FS-H
OFF
-100
1300
ON
Parameter
Factory default
H-SC
1300
L-SC
-100
LOC
OFF
(A)
Photo
electric
sensor
(B)
Fiber
optic
sensor
(C)
MD
Door/Area
sensor
(D)
Proximity
sensor
(E)
Pressure
sensor
(F)
Rotary
encoder
(G)
Connector/
Socket
(H)
Temp.
controller
(I)
SSR/
Power
controller
(J)
Counter
(K)
Timer
(L)
Panel
meter
(M)
Tacho/
Speed/ Pulse
meter
(N)
Display
unit
(O)
Sensor
controller
(P)
Switching
mode power
supply
(Q)
Stepper
motor&
Driver&Controller
(R)
Graphic/
Logic
panel
(S)
Field
network
device
(T)
Software
(U)
Other
H-79