Autonics TC4SP Handmatig - Pagina 5
Blader online of download pdf Handmatig voor {categorie_naam} Autonics TC4SP. Autonics TC4SP 14 pagina's. Touch switch type temperature controller
Ook voor Autonics TC4SP: Handmatig (14 pagina's), Handmatig (2 pagina's), Gebruiksaanwijzing (2 pagina's), Snelstarthandleiding (9 pagina's), Snelstarthandleiding (10 pagina's)
TC Series
Parts description
1
3
2
6
1. Present temperature (PV) display
RUN mode: Present temperature (PV) display.
Parameter setting mode: Parameter or parameter
setting valuedisplay.
2. Deviation indicator, Auto-tuning indicator
It shows current temperature(PV) deviation based on set
temperature(SV) by LED.
No
PV deviation temp.
1
Over 2℃
2
Below ±2℃
3
Under -2℃
Deviation indicator ( ,
when operating auto tuning.
3. Set temperature(SV) indicator
Press any front key once to check or change current set
temperature(SV), set temperature(SV) indicator is on
and preset set value is flashed.
4. Temperature unit(℃/℉) indicator
It shows current temperature unit.
Input type and range
Input sensor
Thermocouple
RTD
Factory default
SV setting
Parameter
Factory default
-
0
Parameter 1 group
Parameter
Factory default
AL1
1250
AL2
AT
OFF
P
01)0
I
0000
D
REST
05)0
HYS
002
H-58
4
5
8
7
Deviation display
lamp on
lamp on
lamp on
,
) is flashed by every 1sec
Display
K(CA)
KCA
J(IC)
JIC
L(IC)
LIC
DPtH
DPt100Ω
DPtL
CUsH
Cu50Ω
CUsL
Parameter 2 group
Parameter
IN-T
UNIT
IN-B
MAvF
L-SV
H-SV
O-FT
C-MD
OUT
SSrM
※ AC/DC power type has no SSR drive output method selection [ SSrM ] function and
supports only ON/OFF output when selecting SSR in control output setting function [ OUT ].
1
2
3
5
5. Control/alarm output indicator
OUT: It will turn ON when control output(Main Control
Output) is ON.
※ In case of CYCLE/PHASE control of SSR drive output,
it will turn ON when MV is over 3.0%. (only for AC
voltage type)
AL1/AL2: It will light up when alarm output Alarm1/
Alarm2 are on.
6.
key
Used when entering into parameter setting group,
returning to RUN mode, moving parameter, and saving
setting values.
7. Adjustment
Used when entering into set value change mode, digit
moving and digit up/down.
8. FUNCTION key
Press
+
keys for 3 sec. to operate function(RUN/STOP,
alarm output cancel) set in inner parameter [ DI-K ].
※ Press
+
keys at the same time in set value
operation to move digit. (only for TC4Y Series)
Input range (℃)
-50 to 1200
-30 to 500
-40 to 800
-100 to 400
-100.0 to 400.0
-50 to 200
-50.0 to 200.0
Factory default
KCA
?C
0000
00)1
-050
1200
HEAT
PID
RLY
STND
7,
6
4
Input range (℉)
-58 to 2192
-22 to 932
-40 to 1472
-148 to 752
-148.0 to 752.0
-58 to 392
-58.0 to 392.0
Parameter
Factory default
T
02)0
AL-1
AMiA
AL-2
AM@A
AHYS
0001
LBaT
0000
LBaB
002
DI-K
STOP
ErMV
00)0
LOC
OFF
8