Autonics krn100 series Handmatig - Pagina 7

Blader online of download pdf Handmatig voor {categorie_naam} Autonics krn100 series. Autonics krn100 series 17 pagina's. 100 mm hybrid recorder
Ook voor Autonics krn100 series: Gebruiksaanwijzing (2 pagina's), Gebruiksaanwijzing (2 pagina's), Producthandleiding (3 pagina's)

Autonics krn100 series Handmatig
KRN100

Part descriptions

Front and side part
①•Display•part:•Displays•measurement•values•as•trend•graph,•bar•graph,•or•digital•number•(1/8/12•channel).•
•••••Please•refer•to「Screen•display」of•the•A-13p.
②•Recording•print•part:•Records•measuring•value•of•data•by•each•channel•with•designated•color.
③•Channel•information•part:•Write•the•information•by•each•channel.•
④•Control•key/Function•key:•Executes•parameter•setting•and•recording,•and•special•function.•
Key
⑤•USB•port•:Connects•an•USB•memory.•It•recognizes•max.•32Gbyte•and•if•using•cable,•it•is•available•up•to•1.5m.
Rear part
A-8
Series
Function
Used•for•starting/stopping•recording,•changing•input•characters•on•virtual•keyboard•status,•and•displaying•Function•
key.•Press•this•key•for•3•sec.•in•stop•state,•the•ink•cartridge•moves•to•the•center.
•(Use•this•key•to•replace•the•ink•cartridge.)
Used•for•going•out•from•parameter•setting•group•or•setting•manual•channel•switch•mode.
It•also•executes•to•release•auto•channel•switch•mode•and•printer•list•output•(3•sec.)•function.•
Used•for•moving•parameter•in•setting•mode,•setting•manual•channel•switch•mode•and•forced•alarm•reset•(3•sec.).
Used•for•moving•parameter•in•setting•mode,•increasing•digit•value,•setting•auto•channel•switch•mode,•and•manual•
feed•function•(by•pressing•over•3•sec.)•in•stop•state.
Used•for•moving•parameter•in•setting•mode,•decreasing•digit•value,•changing•display•mode•and•executing•manual•
digital•memo•(3•sec.)•in•recording•state.
Used•for•entering•setting•mode•(3•sec.)•and•set•value•change•mode.
① Slot(C)•for•connecting•communication•output•card(KRN-COM)
②•Slot(7to10)•for•connecting•digital•input•card(KRN-DI6),•alarm•relay•output•
card(KRN-AR4),•alarm•transistor•output•card(KRN-AT6),•transmitter•power•output•
card(KRN-24V3).
•••••You•can•connect•total•4EA•by•combining•digital•input•card,•alarm•output•card,•and•
transmitter•power•output•card,•as•below•combination•example.
③•Slot(1•to•6)•for•connecting•universal•input•card(KRN-UI2)
④•Power•connecting•part•(100-240VAC•50/60Hz)•
※ • A bove•the•rear•side•image•is•connected•every•otuput•card•to•help•your•understand.
※ • F unction•key:•
• Use•this•key•to•enter•virtual•keyboard•in•parameter•setting.
• Press•the•
•key•and•Function•key•appears•on•lower•screen•as•below•
figure.•Press•the•
,•
key,•it•operates•the•appropriate•Function•key's•operation.
<-Left
Right->
KRN-DI6
KRN-AR4•
+
+
1EA
1EA
KRN-DI6
KRN-AR4•
+
+
2EA
1EA
KRN-DI6
KRN-24V3•
+
=
1EA
3EA
,•
,•
,•
••key•as•below•Function•
Delete
Cancel
OK
KRN-AT6•
KRN-24V3
+
=
1EA
1EA•
KRN-AT6•
=
Total•4EA
1EA
Total•4EA
Total•4EA