Functions
Error
Displays error messages on screen and print data when error occurs.
Message
Description
When input type is temperature sensor (Thermocouple, RTD) and the measurement value is higher
than high-limit value of input range, it flashes HHHH. It is cleared when the measurement value is within
the high-limit range.
HHHH
When input type is analog (voltage, current (shunt)) and the measurement value is over 10% of high-
limit input range, it flashes HHHH. It is cleared when the measurement value is within 10% of high-limit
input range.
When input type is temperature sensor (Thermocouple, RTD) and the measurement value is lower than
low-limit value of input range, it flashes LLLL. It is cleared when the measurement value is within the
low-limit range.
LLLL
When input type is analog (voltage, current (shunt)) and the measurement value is over 10% of low-limit
input range, it flashes LLLL. It is cleared when the measurement value is within 10% of low-limit input
range.
When input type is temperature sensor (Thermocouple, RTD) and input is break, it flashes BURN. It is
BURN
cleared when input is connected.
When forgetting and entering invalid password 3 times, "ASKey" appears with error message. Contact our
ASKey
service center with ASKey.

Factory Default

Display
File History
Menu
History Mode Graph
Memory
File Name
Group Setting
Parameter
Default
CH Rotation
5s
Time
Name
GROUP1
No. of CHs
Auto set
Background
21 (White)
Display CH
Auto set
LCD Touchscreen Paperless Recorder
Default
H Trend
Internal Memory
-
Parameter
Default
Display CH
Auto set
Color
Line Thickness 2Pt
Min. Value
-200.0
Max. Value
1350.0
Input CH Info.
Input/Display
Parameter
Default
Copy
None
Tag Name
CH-1
Input Type
TC-K
Low-Limit
-200.0
Graph Scale
High-Limit
1350.0
Graph Scale
Low-Limit Input Auto set
Input Option
Parameter
Default
Special Func.
None
Ref. CH
-
Two Unit
-
Input Bias
0.0
Span
1.000
Alarm
Parameter
Default
Type
PV.Hi
Ref. CH
-
Option
Normal
Setting Value
1350.0
Hys
0.0
Parameter
Default
High-Limit Input Auto set
Point
0.0
Low-Limit Scale -
Low-Limit Scale -
Display Unit
Parameter
Default
Record Method Instant
Digital Filter
None
No. of
1
Digital Filters
Burn-out Mark
None
Parameter
Default
ON Delay
0s
OFF Delay
0s
Alarm No.
None
Save Event
ON