LE4S Series

LE4S Output Operation Mode

Mode
Time chart
[
OND
]
OND
ON Delay
1. Timing operation starts when START signal is ON at status of power on.
2. Output will be ON when timing operation is progressed up to the setting time. Display value will be
3. When RESET signal is ON, display value and output will be reset. (② position)
T > Ta
4. If RESET signal is OFF while START signal is ON,"STEP 1"will be restarted. (③ position)
5. When START signal is OFF, display value and output will be reset. (④ position)
[
]
ONd1
ONDⅠ
ON Delay 1
1. Timing operation starts when START signal is ON at status of power on.
2. Output will be ON when timing operation is progressed up to the setting time. Display value will be
T > Ta
3. Even though START signal is applied repeatedly, only the initial signal is recognized. (② position)
4. When RESET signal is ON, display value and output will be reset. (③ position)
[
ONd2
]
ONDⅡ
ON Delay 2
1. Timing operation starts when START signal is ON at status of power on.
(One-shot output)
2. Time limit output will be ON and goes OFF during Tout setting time when timing operation is progressed
3. When RESET signal is ON, display value and output will be reset.
4. If START signal is applied while time is progressing, Timing operation will be reset and started again. (②
T > Ta
5. Tout setting range: 0.01 sec to 99.99 sec
[
FLK
]
FK
Flicker
(Toff operation
precedes)
1. If START signal is ON, output will be repeatedly OFF during Toff setting time and will be OFF during Ton
2. When RESET signal is ON, display value and output will be reset.
3. If RESET signal is OFF when START signal is ON, "STEP 1" will be restarted.
4. When START signal is OFF, display value and output will be reset.
Ton, Toff > Ta
5. It is able to set each Toff time and Ton time separately. In [
[
FLk1
]
FK. Ⅰ
RELAY OUT
UP
Flicker 1
DOWN
(Ton operation
1. IF START signal is ON, output will be repeatedly ON during Ton setting time and will be OFF during Toff
precedes)
2. Even though START signal is applied repeatedly, only the initial signal is recognized. (① position)
3. When START signal is ON, display value and output will be reset. If START signal is ON, it will be
Ton, Toff > Ta
4. It is able to set each Toff time and Ton time separately. In [
※ Initial status: UP mode-display value is "0", output is "OFF". DOWN mode-display value is "setting time", output is "OFF".
N-34
T
POWER
START
RESET
RELAY OUT
Setting time
UP
0
Setting time
DOWN
0
HOLD. (① position)
T
POWER
START
RESET
RELAY OUT
Setting time
UP
0
Setting time
DOWN
0
HOLD. (① position)
T
POWER
START
RESET
RELAY OUT
Setting time
UP
0
Setting time
DOWN
0
up to the setting time. Display value will be HOLD. (① position)
position)
Toff
Ton
Toff
POWER
START
RESET
RELAY OUT
Toff
Ton
UP
0
Toff
Ton
DOWN
0
setting time when power is ON.
Ton
Toff
Ton
POWER
START
RESET
Toff
Ton
0
Toff
Ton
0
setting time when power is ON.
restarted.
T
Ta
T
T
Ta
Ta
Toff
Ta
Toff
] mode, timing operation starts with Toff.
Toff
Ta
Ton
Toff
Ta
] mode, timing operation starts with Ton.
T
Ta
T
Ta
T
Ton
Ta
Toff
Ton
Ton
Ta
Ton
T = Setting time, T > Ta
Operation
POWER
START
T
RELAY
OUT
T = set time
POWER
RESET
START
T
RELAY
OUT
T = set time
POWER
START
Tout
RELAY
T
OUT
Tout = output time
T = set time
POWER
START
Toff Ton Toff Ton
RELAY
OUT
Ton, Toff = set time
Enables to set Ton and
Toff time differently.
POWER
START
Ton Toff Ton
RELAY
OUT
Ton, Toff = set time
Enables to set Ton and
Toff time differently.