2HEAT RF Series Gebruikershandleiding - Pagina 5

Blader online of download pdf Gebruikershandleiding voor {categorie_naam} 2HEAT RF Series. 2HEAT RF Series 11 pagina's.

Application...
Program presetting when out of factory:
From Monday to Friday
00:00-----06:00 Economic temperature
06:00-----08:00 Comfort temperature
08:00-----18:00 Antifreeze temperature;
18:00-----22:00 Comfort temperature
22:00-----24:00 Economic temperature
Saturday and Sunday
00:00-----06:00 Economic temperature; 06:00-----22:00 Comfort temperature
22:00-----24:00 Economic temperature
2
"Manual" mode
The chronothermostat controls the temperature at a constant temperature mode, and the
default temperature is 20
and the temperature display flashes at this time. The screen will recover to display the room
actual temperature when there is no further adjustment within 5 seconds.
Note:
When moving the function change-over switch position every time and when
resetting the manual temperature is needed, the system will automatically start to set from
the manual mode that was set last time, and the state display circular at the right lower
corner will completely display double frames.
3
"Antifreeze" mode
The chronothermostat only controls the system to be operated at the state of preventing the
ambient temperature from dropping below the antifreeze temperature to have been set in
order to make the equipment and pipes free from freezing. This temperature is set in the
mode of "Temperature setting", and the default valve is 5 .
. The temperature can be adjusted with
key or
>4
key