Gallagher T12 Installatie Opmerking - Pagina 6

Blader online of download pdf Installatie Opmerking voor {categorie_naam} Gallagher T12. Gallagher T12 13 pagina's.
Ook voor Gallagher T12: Installatie Opmerking (11 pagina's), Handmatig (12 pagina's)

Gallagher T12 Installatie Opmerking
HBUS
Device
Terminate
HBUS
Device
Terminate
Cable distance
Cable type
CAT 5e or
better**
BELDEN 9842**
(shielded)
SEC472
SEC4142
* The matching of wire sizes to equivalent wire gauges are only approximate.
3E4290 Gallagher T12 Reader | Edition 1 | August 2016
Copyright © Gallagher Group Limited
"T" or "Star" circuits are
HBUS
not permitted between
Device
HBUS devices
RS485 1
HBUS
Device
Controller 6000
Remove the on-board
termination jumper
"T" or "Star" circuits are
HBUS
not permitted between
Device
HBUS devices
Controller 6000
H1
HBUS
H5
Device
HBUS Module
HBUS
Device
Terminate
Cable format*
HBUS
single reader
connected using
data only in a
single cable
4 twisted pair
500 m (1640 ft)
Each 2 x 0.2 mm
2
(24 AWG)
2 twisted pair
500 m (1640 ft)
Each 2 x 0.2 mm
2
(24 AWG)
4 x 0.2 mm
400 m (1310 ft)
2
Not twisted
pairs (24 AWG)
4 x 0.4 mm
400 m (1310 ft)
2
Not twisted
pairs (21 AWG)
HBUS
Device
H4
H8
HBUS
Device
HBUS
Device
Terminate
Cardax IV
single reader
connected using
data only in a
single cable***
200 m (650 ft)
200 m (650 ft)
200 m (650 ft)
200 m (650 ft)
HBUS
Device
Terminate
HBUS
Device
Terminate
HBUS/Cardax IV
single reader
connected using
power and data
in a single cable
100 m (330 ft)
100 m (330 ft)
100 m (330 ft)
150 m (500 ft)
Page 6