AGS Merlin FAM 1 Installatie- en bedieningshandleiding - Pagina 7
Blader online of download pdf Installatie- en bedieningshandleiding voor {categorie_naam} AGS Merlin FAM 1. AGS Merlin FAM 1 8 pagina's. Gas service manual reset controller
FAM1
Specifications
General
Model:
Size: (H x W x D)
Housing Material:
Mounting:
Weight:
User Interface
Visual Indicators:
Audible Alarm:
Buttons:
Language:
Power Supply
Power Consumption:
AC IN Power:
Internal Fuse:
Equipment
Overvoltage Category:
Pollution Degree:
Relays
Dry Contact BMS relay output:
Environmental
Ingress Protection:
Operating:
Storage:
Altitude Rating:
Wiring
Typical
Compliance
Electrical Safety and Electromagnetic Compatibility
Rev: 01
04-23
AGS FAM1
5.51 x 7.48 x 2.44" (140 x 190 x 62mm)
ABS PA765 (Flame Rating UL94 V-1)
Safe Zone - Indoor use - Wall Mounted
2.2lb (1.0kg)
3 LED – POWER / GAS ON / EM STOP / FIRE ALARM LOCKOUT
70dB @ 3.28ft (1m). Quiet conditions.
None
English
1.2W max
100-120V~ 50/60Hz
Anti-Surge 3.15A 250Vac
II
2
0.5A switching current (resistive load)
IP 6X Not Formally Evaluated
-10 ~ 50°C / 14 ~ 122°F 30 ~ 80% RH (non-condensing)
-25 ~ 50°C / -13~122F° up to 95% RH (non-condensing)
2000m
Min. 18AWG / 75°C min / Tinned copper.
IEC 61010-1
EMC EN 61326-1:2013
Installation & Operation Manual
7