AGS Parksafe Control Panel Installatie-, bedienings- en onderhoudshandleiding - Pagina 19
Blader online of download pdf Installatie-, bedienings- en onderhoudshandleiding voor {categorie_naam} AGS Parksafe Control Panel. AGS Parksafe Control Panel 20 pagina's. Ventilation control panel
Ook voor AGS Parksafe Control Panel: Installatie- en bedieningshandleiding (16 pagina's), Installatie- en bedieningshandleiding (16 pagina's), Installatie, bediening en onderhoud (16 pagina's)
Installation, Operation & Maintenance
Specification
General
Model:
Capacity:
Size: (H x W x D)
Housing Material:
Mounting:
Weight:
User Interface
Display:
Screen Brightness:
Visual Indicators:
Audible Alarm:
Buttons:
Language:
Power Supply
Power Consumption:
AC Power:
Internal Fuse:
Equipment
Overvoltage Category:
Pollution Degree:
Equipment Class:
I/O
Relay Output:
Common Output:
Environmental
Ingress Protection:
Operating:
Storage:
Altitude Rating:
Wiring
Typical
Approvals
Electromagnetic Compatibility and
Electrical Safety
Other
Communication
Rev: 20
ParkSafe Controller
Up to 16 channels per controller unit.
7.08 x 10.03 x 3" (180 x 255 x 77 mm)
ABS Polylac - PA765.
UL 94 V-1
Indoor use - Wall Mounting
1.3kg (2lb 13.85oz)
4.3" TFT Touch Screen
Adjustable 0-100%
TFT visual. Green: Normal; Yellow: Pre-Alarm; Amber: Alarm Delay: Red: Alarm
Relay Outputs On/Off
Gas Detection Status.
>70dB @ 3.28ft (1m). Quiet conditions.
Common for Silence/Reset operation.
English
14.5W max.
100-120V~ 50/60Hz
T3.15A L250V
II
2
2
Volt Free Relay Outputs x4 (non-latching).
NO/C/NC 6A @ 120V~
User configurable – energised/de-energised, time delay.
24 VDC switching.
24 VDC Permanent.
0-10 VDC Variable.
Not Formally Evaluated
-10 ~ 50°C / 14 ~ 122°F 30 ~ 80% RH (non-condensing)
-25 ~ 50°C / -13~122F° up to 95% RH (non-condensing)
2000m
Power~#18-12AWG-Tinned Copper.
Current Rating: 1A Minimum. Voltage:100-250V~. Wire Stripping Length 6-7mm
Relay: ~#18-12AWG-Tinned Copper.
Current Rating: 10A Minimum. Voltage: 100-250V~ Wire Stripping Length 6-7mm
For field connections use wires suitable for at least 90°C (194°F)
Detector: #15AWG Power Pair
Other: #18-14AWG-Tinned Copper.
IEC 61010-1:2010 + AMD1:2016; EN 61010-1:2010 +A1:2019; UL61010-1/2012/R:2019-07;
CAN CSA C22.2 No. 61010-1-12/A1:2018-11
EMC EN 61326-1:2013
RS485 MODBUS RTU
#18AWG Data Pair-Tinned copper.
ParkSafe Controller
19