Galvin Engineering CliniLever TCWTC150HC Product Installatie Manuallijn - Pagina 3

Blader online of download pdf Product Installatie Manuallijn voor {categorie_naam} Galvin Engineering CliniLever TCWTC150HC. Galvin Engineering CliniLever TCWTC150HC 4 pagina's. Cp-bs hospital wall top assembly

Product Installation Guidelines
3. Fit handle
Ensure the spindle is in the closed position and
firmly press the lever handle onto the spindle in
the desired orientation.
Check lever handles for correct operation. It
should turn freely for a full ¼ turn.
Secure the handle in position using the
supplied washer and stainless steel cap screw.
TROUBLESHOOTING
PROBLEM
Taps are dripping water
Water is leaking from spindle
Water is not flowing from tap
Spindle is difficult to turn
(jumper valve)
Handle is loose
© Galvin Engineering Pty Ltd
4. Fit water temperature indicator & testing
CAUSE
Jumper valves are worn or damaged
Tap seat is damaged
O-ring on jumper valve spindle is
damaged or worn
Water is turned off
Aerator or flow regulator is blocked by
debris
Build up of scale on spindle, spindle
worn or o-ring has been damaged
Screw has come loose
Once lever handle is secure; fit the appropriate
water temperature indicator.
Once temperature indicator is fitted, check the
operation of the unit and inspect for any leaks.
RECTIFICATION
Replace jumper valve
Refurbish tap seat using a reseating
tool.
Replace o-ring
Turn on water
Remove aerator and/or flow
regulator from tap and remove
debris. Install an inline strainer.
Remove jumper valve, clean and
regrease. Replace o-ring. Complete
SBA may need to be replaced.
Tighten handle screw
Document No.: 001.00.10.18
Version 1, 4 November 2022, Page 3 of 4