7. Assemble handle
−
Fit handle with tamper proof screw, ensure the
correct water temperature identification button
is in the handle
−
Screw must be tightened before the unit is
tested
TROUBLESHOOTING
PROBLEM
Taps are dripping water
Water is not flowing from tap
8. Testing
−
CAUSE
Ceramic cartridge is worn or
damaged
Water is turned off
Version 1, 10 November 2016, Page 3 of 4
Once temperature indicator is fitted, check the
operation of the unit and inspect for any leaks.
RECTIFICATION
Remove and inspect the cartridge, remove
debris and /or replace cartridge if damaged
Turn on water