Installation, Operation & Maintenance
MIN 0-10 OUT 1
Analogue output minimum voltage.
Select:
0, 1, 2, 3, 4, 5
volt/s
MIN 0-10 OUT 2
Analogue output minimum voltage.
Select:
0, 1, 2, 3, 4, 5
volt/s
0-10V OUT 1
0-10V analogue output energised by.
Select:
CO2 / TEMPERATURE / DUAL
0-10V OUT 2
0-10V analogue output energised by.
Select:
CO2 / TEMPERATURE / DUAL
BUZZER
Kitchen Vent Type Mode
CO
>2800ppm Only. Select:
2
ON
– 3 beeps every 15 seconds
10MINS
– 3 beeps every 10 minutes
OFF
TEMP. UNITS
Temperature measurement
Select:
°C
Celsius /
°F
Fahrenheit

Factory Set Condition

VENT. TYPE
MIN 0-10 OUT 1
MIN 0-10 OUT 2
0-10V OUT 1
0-10V OUT 2
Rev 5 10-21
BOOST (MIN.)
Analogue outputs at optimum voltage
(10V) for number of minutes. Boost can be activated only if analogue
outputs are set to either CO2 or DUAL mode only.
Select:
FAN ENABLE
Fan switch is energised by.
CO2
TEMPERATURE
DUAL
BRIGHTNESS
Brightness of the screen display. Select:
LOW / MEDIUM / HIGH
SCREEN SAVER
ON
alarm/ alarm status.
OFF
TEMP. ADJUSTMENT
Adjust the temperature display by up to ± 5°C or 9°F in increments of
0.1°
FACTORY RESET
Return to default condition.
YES / NO
KITCH.
BUZZER
1
TEMP. UNITS
1
BOOST (MIN.)
TEMP
FAN ENABLE
CO2
BRIGHTNESS
1, 2, 3, 4, 5, 6, 7, 8, 9, 10
(ON >600ppm OFF <550ppm)
(ON >23°C OFF <22°C)
(Whichever is greatest)
– screen will switch off until temperature or CO
– screen constantly on.
ON
SCREEN SAVER
°C
TEMP. ADJUSTMENT
1
CO2
MED
FACTORY RESET
Merlin CO2-X
minute/s
levels reach pre
2
OFF
0.0°C/F