AGS Merlin 1000S Gebruikers- en installatiehandleiding - Pagina 5
Blader online of download pdf Gebruikers- en installatiehandleiding voor {categorie_naam} AGS Merlin 1000S. AGS Merlin 1000S 10 pagina's. Gas utility isolation controller
Ook voor AGS Merlin 1000S: Installatie-, Bedienings- en Onderhoudshandleiding (10 pagina's), Installatie- en bedieningshandleiding (12 pagina's), Installatie- en bedieningshandleiding (16 pagina's)
Merlin 1000S
(7)
[FS1/2/3/4]
Fan Switch Output
This terminal switches when the key is turned on and off. This can be linked to a fan switch
(panel supplied separately) which can provide power to fans when the control panel is
switched on.
(8)
[CO2 MONITOR]
CO
Monitor
2
This terminal can be wired to CO
system in the event of High CO2 levels.
If no CO
monitor is supplied leave the terminal link in [
2
(fig3)
(9)
[12VDC]
12v DC Output
This is a permanent 12v DC output when there is power at
the panel and can be used to create a relay switch with the
BMS relay output. Please contact your supplier for further information.
Use a screened cable to avoid electrical interference between HIGH & LOW VOLTAGE connections
Internal Buzzer
Operates at 65dB measured 30cm from closed panel.
Panel Timeout Facility
The Merlin 1000S has a built-in Auto-shut down feature and it will turn itself off after a
predefined time. Auto-shut down timeout is selectable.
There are two Dip-Switches located on the inside facia of the Merlin 1000S labelled [Time1]
and [Time2]. (fig4) The gas supply will be cut off at desired time-out.
To select required timeout – configure Dip Switches as follows;
2 HOURS (FACTORY SET)
Time1 Off / Time2 Off
4 HOURS
Time1 On / Time2 Off
8 HOURS
Time1 Off / Time2 On
NO TIMEOUT
Time1 On / Time2 On (auto-shut down disabled)
Rev: 04 Date: 15-08-18
Gas Utility Controller
monitor to shut off the
2
User & Installation Manual
fig3
].
fig4
5