Generic 4-20mA Sensor Wiring:
1. Wire colors likely will be different in your application, please compare your sensor colors
to the sensor functions listed below, and do not solely rely on the colors shown above!
2. 4-20mA Sensor must be 12v compatible.
3. Install the Sensor Power wire into the 12v Out terminal as shown with the red wire
example above.
4. Install the Sensor Ground and Sheild wires (if your sensor has them) into the GND
terminal as shown with the green wire example above
5. Install the Sensor 4-20mA Signal wire into input Analog5 4-20mA terminal (or Analog 6
4-20mA terminal) as shown with the black wire example above.
6. Make sure a jumper is installed as shown above (J16 if using Analog 5, or J18 if using
Analog 16) or the 4-20mA input will not work.
7. Remember to log into the user website, and select the 4-20mA Input from the dropdown
in the Config page for this unit, and fill in the values this sensor will have at 4mA and
20mA, enter the units this reflects, and then save the settings.