This booklet is an integral and essential part of the product and must be delivered to the
user. Carefully read the warnings contained inside that provide important information
regarding safety during installation, use and maintenance.
OVERVIEW
The DEA 203_2 control panel has been designed to control the "DEA SYSTEM" automa-
tion devices for both sliding gates and garage doors powered by 230V single-phase
motors, and comes complete with electronic motor
control for the detection of any obstacles present and an inertia limitation system for
use with sliding gates. The widest versatility, easy installation and complete respect for
the European regulations in force regarding electromagnetic compatibility and electric
safety are the unit's main characteristics; in particular, DEA SYSTEM ensures conformity
to the following European Directives: 89/336/EEC, 73/23/EEC and subsequent amend-
ments.
DEA SYSTEM reminds all users that the selection, configuration and installation of all the
devices and materials in the entire automation must be performed in respect of the
regulations in force in the nation of installation.
TECHNICAL DATA
Power supply
Flashing light output
Gate open signal light/courtesy light output
Auxiliary power supply output
Electric lock output
Max. motor power
Fuse F1
Fuse F2
Max pause time
Max work time
The work time you set must anyway allow to respect the maximum working time admit-
ted for the type of motor you are using. Please refer to the data on the motor label.
ELECTRICAL SYSTEM CONFIGURATION
(See fig. 1)
IMPORTANT: Any installation, maintenance, cleaning or repair operations on any part
of the automatism must be performed exclusively by qualified personnel, and all such
operations must be performed only after first disconnecting the power supply. Always
keep the 230V cables (power supply, motor, starting condenser, flashing light, courtesy
light) separate from the low voltage cables (controls, electric lock, antenna, and auxil-
iary power supply) and fasten these latter using adequate clamps near the terminal
boards. Install a multiple pole switch with a contact opening of 3 mm provided with
protection against overloads upstream from the automatism. Use a cable with a mini-
mum section of 3X1.5 mm² (such as H07RN-F type) for the power supply and scrupu-
lously respect all the regulations in force regarding electrical systems in the nation of
installation.
TERMINAL BOARD CONNECTION:
(See fig. 1)
1-2:
Power supply: 230V AC +/-10% 50 Hz (F = phase, N = neutral)
3-4
Courtesy light output 230 V AC 50 Hz max 40W (DIP8 = ON)
Gate open indicator light output: 230 V AC 50 Hz max 40W (DIP8 = OFF)
5-6
Flashing light output: 230 V AC 50 Hz max 40W
7-8-9
Motor output (7 = open, 8 = common, 9 = close)
10-11
electric lock output 12V AC 15VA
12
Common inputs
13
FCA opening limit-switch input (N.C.) stops the motor's opening stroke
14
FCC closing limit-switch input (N.C.) stops the motor's closing stroke
15
APRE PEDONALE opens the gate to a width of only 1.5 (N.O.)
16
FOTO Photocell Art. 104/105 input (N.C) inverts movement during closing, and
if enabled during opening stops movement
17
STOP stop button input (N.C) stops movement in any situation
18
APRE open/close button input (N.O.) can function in both step-by-step mode
and inversion mode
IMPORTANT: All N.C. inputs not used must be bridged towards the common inputs
terminal.
19
Antenna ground
20
Antenna signal
21-22
Auxiliary power supply output: 24V AC max 200mA
J3
Radio receiver plug-in connector
OPERATION:
TIME SETTING
TCA
trimmer for the setting of the automatic closing time, after which the gate will
automatically close again.
TLAV
trimmer for the setting of the work time, after which the motor will stop during
both opening and closing.
Whenever the limit-switches are installed, the work time must be set to a value
that is a few seconds higher than the real time required for the stroke of the
motor.
force adjustment, amperometer
230V AC +/- 10% 50 Hz
:230V AC 50 Hz max 40W
:230V AC 50 Hz max 40W
:24V AC max 200 mA
:12V AC max 15V A
:500W
:160 mA 250V
5A
250V
:80 s
:160 s (sliding version)
:80 s (garage door version)
GB
DIP-SWITCHES FUNCTIONS
ON
"collectivity"
function enabled: does not receive opening pulses
during opening and the gate open pause time
DIP1
OFF
"collectivity"
function disabled: receives opening pulses also during
opening and the gate open pause time
ON
See description "reverser operation"
DIP2
OFF
See description "reverser operation"
ON
"step-by-step" program: OPEN->opening, OPEN->stop, OPEN-
>closing...
DIP3
OFF
"inversion" program: OPEN->opening, OPEN->closing, OPEN-
>opening...
ON
Sliding version: closing limit-switch delay disabled, anti-inertia de-
vice enabled
DIP4
OFF
Garage door version: closing limit-switch delay enabled, anti-inertia
device disabled
DIP5
ON
Photocell operative also during opening: stops all movement until the
obstacle is removed
OFF
Photocell operative only during closing: inverts direction of movement
ON
automatic closing disabled: after opening, it closes again only after
an opening pulse
DIP6
automatic closing enabled : after opening, and after the pause time
OFF
set, the gate automatically closes again
DIP7
ON
Reverser disabled
OFF
Reverser enabled.
ON
Terminals 3-4: courtesy light output 230V AC 50 Hz (delay: 50 sec-
onds)
DIP8
OFF
Terminals 3-4: gate open signal light output, 230V AC, 50 Hz
FORCE ADJUSTMENT
The 203_2 control panel is equipped with a device that permits the electronic adjust-
ment of motor force by adjusting the "forza" trimmer:
"FORZA":adjusts the intensity of the motor force during the stroke (rotate
clockwise to increase force, counter-clockwise to decrease force).
The motor force must be adjusted by keeping trimmer R32 "SENS" in
the MIN. position (entirely in clockwise direction) in order to avoid
the undesired intervention of the REVERSER. The sensitivity of the
reverser is made subsequently (see "Reverser operation").
REVERSER OPERATION
Whenever the "reverser" device is used, the limit-switches must also be installed
After setting the motor force, proceed to the setting of reverser sensitivity. Make sure
that the reverser is enabled (DIP7 OFF) and with the sensitivity set at minimum level
(trimmer R32 turned entirely clockwise) perform an opening movement. During closing,
stop the gate and slowly increase the reverser sensitivity (trimmer R32 turned counter-
clockwise) until the reverser intervenes
permits the identification of the sensitivity necessary for the intervention of the re-
verser as soon as the motor stops.
In any case, we recommend setting a sensitivity that is SLIGHTLY lower in order to
avoid the undesired intervention of the reverser by mechanical friction.
The position of DIP2 determines the reaction to the perception of the obstacle, and in
particular:
•
DIP 2 ON : during both opening and closing, the intervention of the reverser
inverts the direction of movement for 3 seconds and then stops it.
•
DIP 2 OFF : during opening, the intervention of the reverser stops movement,
and during closing inverts the direction of movement.
It is in any case obligatory to use appropriate safety devices in order to ensure the
impact force limitation values prescribed by the regulations in force in the nation of
installation.
IMPORTANT: limit-switches compulsory
(inversion of direction of movement). This