Gree GMV BACnet Technisch en onderhoudshandboek - Pagina 16
Blader online of download pdf Technisch en onderhoudshandboek voor {categorie_naam} Gree GMV BACnet. Gree GMV BACnet 20 pagina's.
2.1.1 BACnet GATEWAY CONFIGURATION
One BACnet gateway connects 16 systems and 255 IDUs at the same time. The gateway
parameter shall be configured after its installation, however, before this please set the IP address
of the PC the same with that of the BACnet gateway, see Attachment A; then open browser (IE10
or higher, Firefox or Google), input the default IP address into the address field:
http://192.168.1.150, the default user name and password are both "config"; refer to the following
fig.
After input, press the button to go to the setting page.
The configurable parameters include BACnet gateway IP address, gateway subnet mask,
gateway default gateway, gateway name, gateway ID. The user can conduct configuration at his
will, after that, click button and it will take effect after resarted Gateway.
2.2 COMMUNICATION DEBUG WITH BMS SYSTEM EQUIPMENT
Protocol interface: BACnet protocol
Hardware interface: Ethernet
GMV BACnet Gateway Technical Service Manual
13