ERROR CODES

CODE
EXPLANATION
E
0001
Exhaust Fan Error
E
0002
Supply Fan Error
E
0004
Electrical Heater Error
E
0008
Exhaust Air Flow Error
E
0016
Supply Air Flow Error
Connection Error between
E
0099
Controller and Card
E
0256
Fire Alarm
TROUBLE SHOOTING
Check the fan,connection cables and filter.If all are fine,
reset the alarm by pressing
simultaneously If there is a broken component replace it
with a new one.
Check the fan,connection cables and filter.If all are fine,
reset the alarm by pressing
simultaneously If there is a broken component replace it
with a new one.
Check the electrical heater and connection cables ..If all
are fine, reset the alarm by pressing
buttons simultaneously If there is a broken component
replace it with a new one.
Check the exhaust fan,connection cables ,filter and
ducting..If all are fine, reset the alarm by pressing
and
UP
buttons simultaneously If there is a broken
component replace it with a new one.If there is an
obstacle at the duct systemi, clean it a for a better air
flow.
Check the exhaust fan,connection cables ,filter and
ducting..If all are fine, reset the alarm by pressing
and
UP
buttons simultaneously If there is a broken
component replace it with a new one.If there is an
obstacle at the duct systemi, clean it a for a better air
flow.
Check connection cables between controller and the
board
Check if there is fire or not.. If the alarm is because of a heat
transmitter close to room thermostate , or another factor that
increases the temperature at the room artificially, make sure
that the room thermostate reads the temperature at the normal
conditions. Also check the electrical heater at the duct system.
If everything is controlled then reset the alarm by pressing
FAN
and
UP
buttons simultaneously.
FAN
and
UP
buttons
FAN
and
UP
buttons
FAN
and
UP
FAN
FAN