IMPORTANT – FOR YOUR PROTECTION.
Electricity is dangerous and an RCD must not be used as a substitute for normal precautionary measures. Always unplug from mains
supply before any inspection or repair to equipment. Do not allow children to tamper with electrical devices.
This device will protect against live and neutral leakage faults to earth, it will not protect against electric shock due to contact with
both conductors, short circuits between live and neutral, or a fault in the wiring supplying this device.
Should your PowerBreaker RCD socket, trip when first powered, repeatedly trip with an appliance connected or fail to trip when
tested in accordance with the instructions, Do Not Use, please consult a qualified Electrician. Type A RCDs are suitable for use with
single phase supplies and applications with electronic components, they are also suitable for type AC RCD applications with
Resistive, Capacitive, Inductive loads generally without any electronic components.
Type AC RCD should not be fitted upstream of a Type A as the load characteristics of a Type A RCD could then impair operation of
the Type AC RCD.
TO FIT THIS POWERBREAKER RCD SWITCHED SOCKET -
To install please follow details below using the easy to follow wiring diagram Fig.1.
Cut out panel - Please see overleaf for a scale drawing of the skeleton socket.
1.
2.
Mount unit on rear face with screws/weld studs as required.
3.
On final assembly stick test label (Fig.2) on front face plate close to operating buttons, and warning label (Fig.3)
close to socket for wiring insulation tests.
4.
This unit should only be operated with front panel in place.
If earth conductors are bare, they must be sleeved with appropriate green/yellow sleeving. If you are in any doubt about
connecting this product consult a qualified electrician.
Note: Green/yellow earth wire may be connected to either earth terminal. Wiring insulation tests should be
completed before setting the PowerBreaker RCD Socket to avoid misleading instrument readings and possible internal damage to
the unit.
Blue (N)
Mains
or Black
Supply
This socket has been designed for storage and use between -5°C and +40°C and at an altitude
of no greater than 2000 metres above sea level. Care must be taken not to subject the unit to
misuse, such as abnormal pollution by smoke, chemical or flammable fumes, salt laden spray,
prolonged periods of high humidity or other abnormal conditions.
Guarantee
Your PowerBreaker Safety RCD
Skeleton Socket is
guaranteed for 12 months.
Each unit is individually tested
before leaving the factory.
Fig.1
Brown (L)
or Red
Green/Yellow (E)
WEST ROAD . HARLOW
ESSEX . CM20 2BG . UK
i n f o @ g r e e n b r o o k . c o . u k
w w w. g r e e n b r o o k . c o . u k
Installation/Operating Instructions for
Safety RCD Single Switched Socket Skeleton
INSTALLATION
This product is designed for panel mounting.
Fig.2
Test each time before use.
Press test button, Red
indicator
should disappear.
NOT
If not do
use.
IP40
30mA trip
Red-On
Current
Green-Off
TEST PROCEDURE
MODEL NO - K21S-WP
This label to be fixed to the consumer unit.
PEEL HERE
IMPORTANT
DISCONNECT POWERBREAKER
RCD UNIT PRIOR TO
WIRING INSULATION TESTS
TECHNICAL INFORMATION
Rated voltage:
Maximum operating current: 13A (13A inductive)
Rated trip current:
Trip speed:
RCD contact break:
Mechanical latching:
Degree of protection:
Rated Short-circuit breaking
and making Capacity:
Rated conditional
short-circuit current:
Independently tested to:
Fig.3
230V AC~50Hz
30mA
Less than 20mS (typical)
Double pole
Passive
IP40
250A
1500A Power factor
Range .93 to .98
BS 7288:2016
BS 1363-2:2016