IKEA IH3302WQ0 Gebruiks- en onderhoudshandleiding - Pagina 6

Blader online of download pdf Gebruiks- en onderhoudshandleiding voor {categorie_naam} IKEA IH3302WQ0. IKEA IH3302WQ0 24 pagina's. 30" (76.2 cm) and 36" (91.4 cm) range hood installation instructions

Example vent system
90° elbow
i_ -
I
6. (1,8
w.lJ
cap
m
m)
Maximum Recommended
Length
= 50 ft (15.2 m)
1 - 90 ° elbow
1 - wall cap
8 ft (2.4 m) straight
Length of 7" (17.8 cm) system
= 5.0 ft (1.5 m)
= 0.0 ft (0.0 m)
= 8.0 ft (2.4 m)
= 13.0 ft (3.9 m)
3Y4"x 10" (8.3 cm x 25.4 cm) Vent System
Vent Piece
7" (17.8 cm) Round
31/4"x 10" (8.3 cm x 25.4 cm)
5.0 ft
90 ° elbow
(1.5 m)
31/4"x 10" (8.3 cm x 25.4 cm)
12.0 ft
flat elbow
(3.7 m)
31/4"x 10" (8.3 cm x 25.4 cm)
0.0 ft
wall cap
(0.0 m)
Example vent system
31/4,, x 10 ,,
(8.3 x 25.4 crn)
elbow
6 ft (1.8 rn)
/
2.q j
I
Maximum Recommended
Length
Wall cap
= 35 ft (10.7 m)
1 - 90 ° elbow
8 ft (2.4 m) straight
1 - wall cap
Length of 31/4 '' x 10" (8.3 cm x 25.4 cm)
system
= 5.0 ft (1.5 m)
= 8.0 ft (2.4 m)
= 0.0 ft (0.0 m)
= 13.0 ft (3.9 m)
& equ
s
Observe all governing codes and ordinances.
Ensure that the electrical installation is adequate and in
conformance
with National Electrical Code, ANSl/NFPA 70 (latest
edition), or CSA Standards C22.1-94, Canadian Electrical Code,
Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes
and ordinances.
If codes permit and a separate ground wire is used, it is
recommended
that a qualified electrician determine that the
ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch
Park
Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
A 120 Volt, 60 Hz., AC only, 15-amp, fused electrical circuit is
required.
If the house has aluminum wiring follow the procedure below:
1. Connect a section of solid copper wire to the pigtail
leads.
2. Connect the aluminum wiring to the added section of
copper wire using special connectors
and/or tools
designed and UL listed for joining copper to aluminum.
Follow the electrical connector manufacturer's
recommended
procedure. Aluminum/copper
connection must conform with
local codes and industry accepted wiring practices.
Wire sizes and connections
must conform with the rating of
the appliance as specified on the model/serial
rating plate.
The model/serial
plate is located behind the filter on the rear
wall of the hood.
Wire sizes must conform to the requirements of the National
Electrical Code, ANSl/NFPA 70 (latest edition), or CSA
Standards C22.1-94,
Canadian Electrical Code, Part 1 and
C22.2 No. 0-M91 (latest edition) and all local codes and
ordinances.
6