IKEA IH3402YS0 Installatie-instructies en gebruiks- en onderhoudshandleiding - Pagina 6

Blader online of download pdf Installatie-instructies en gebruiks- en onderhoudshandleiding voor {categorie_naam} IKEA IH3402YS0. IKEA IH3402YS0 40 pagina's. 30" (76.2 cm) range hood

Cold Weather
Installations
An additional back draft damper should be installed to minimize
backward cold air flow and a thermal break should be installed to
minimize conduction of outside temperatures
as part of the vent
system. The damper should be on the cold air side of the thermal
break.
The break should be as close as possible to where the vent
system enters the heated portion of the house.
Makeup
Air
Local building codes may require the use of makeup air systems
when using ventilation systems greater than specified CFM of air
movement. The specified CFM varies from locale to locale.
Consult your HVAC professional for specific requirements in your
area.
Venting Methods
Vent system can terminate either through the roof or wall. Use
7" (17.8 cm) or larger round vent with a maximum length of
50 ft (15.2 m) for vent system.
NOTE: Flexible vent is not recommended.
Flexible vent creates
both back pressure and air turbulence that greatly reduce
performance.
Roof Venting
A
.........................
f
--
Wall Venting
I ;
?
C
A. 7" (17.8 cm) round vent
through roof
(purchased separately)
B. Roof cap with damper
(purchased separately)
C. 18" (45.T cm)min,
to
24" (61.0 cm) max. above the
cooking surface
A. 7" (17.8 cm) round vent out
the top and through the wall
(purchased separately)
B. Wall cap with damper
(purchased separately)
C. 18" (45.T cm) min. to
24" (61.0 cm) max. above the
cooking surface
Calculating
Vent System
Length
To calculate the length of the system you need, add the
equivalent feet (meters) for each vent piece used in the system.
7" (17.8 cm) Round Vent System
Vent Piece
Round
45° elbow
2.5 ft
(0.8 m)
90 ° elbow
5.0 ft
(1.5 m)
7" (17.8 cm) wall cap
0.0 ft
(0.0 m)
31/4"x 10" (8.3 cm x 25.4 cm)
4.5 ft
to 7" (17.8 cm)
(1.4 m)
31/4"x 10" (8.3 cm x 25.4 cm)
5.0 ft
to 7" (17.8 cm) 90 ° elbow
(1.5 m)
Example vent system
7" (17.8 cm) round
90 ° elbow
Wall
cap
=T=
2 ft (0.6rn)
_!=
6 tt (1.8 m)
Maximum Recommended
Length
= 50 ft (15.2 m)
1 - 90 ° elbow
1 - wall cap
8 ft (2.4 m) straight
Length of 7" (17.8 cm) system
= 5.0 ft (1.5 m)
= 0.0 ft (0.0 m)
= 8.0 ft (2.4 m)
= 13.0 ft (3.9 m)
6