Top Framing and Finishing: Combustible framing materials
requires 3/4 inch to top of firebox. See Figure 1.
Sidewall Clearances: The clearance from the inside of the firebox
to perpendicular combustible side wall should not be less than
6 inches. See Figure 2.
Firebox Face Clearance: 3/8 inch from face and back 1 3/4 inches.
Firebox Side and Back Clearances: The firebox outer casing side
and back flanges are zero clearance to combustibles.
Firebox Front Clearance: Leave at least 36 inches clearance from
the front of the firebox into the room.
Ceiling Clearances: The ceiling height should not be less than
84 inches from the floor. See Figure 3.
Mantel Clearances: Firebox models must use the hood supplied
with the firebox, or the optional extension hood available for
each model. If a combustible mantel is installed, it must meet the
clearance requirements detailed in Figure 3.
Grate Clearance: The minimum clearance between the front legs
of the grate and front edge of the firebox is 2 inches.
1 3/4"
Page 8

CLEARANCES

OUTER WRAPPER
FIREBOX WALL
FRONT FACE (SIDE)
3/8" GAP REQUIRED
BOTH SIDES
2 X 4
TOP PLATE
Figure 1 - Clearances to Combustibles
FIREBOX
(TOP VIEW)
3"
MAX.
PERPENDICULAR
SIDE WALL
Figure 2
COMBUSTIBLE
FINISHED WALL
OR MANTEL
NON-COMBUSTIBLE
BOARD OR FACING
3/4" GAP REQUIRED
ACROSS ENTIRE TOP
OF FIREPLACE
COMBUSTIBLE
MATERIALS ALLOWED
IN SHADED AREAS
45°
6"
MIN.