5. FINISHING
Install the insulated pipes so that they do not touch the compressor.
5.1. Installing insulation
• Install insulation material after conducting "3.6. Sealing test".
• To prevent condensation and water droplets, install insulation material on the refrigerant
pipe. (Fig. A)
• Refer to the table to determine the thickness of the insulation material.
Selection of insulation
(Use an insulation material with equal heat transmission rate or below 0.040
W/(m·k))
Relative humidity
[in (mm)]
1/4 (6.35)
3/8 (9.52)
1/2 (12.70)
Pipe
5/8 (15.88)
diameter
3/4 (19.05)
7/8 (22.22)
1 (25.40)
* When the ambient temperature and relative humidity exceed 89.6 °F (32 °C) (DB) and
85% respectively, strengthen the heat insulation of refrigerant pipe.
5.2. Filling with putty
Fill the piping holes and wiring holes with putty (locally purchased) to avoid any gap
(Fig. A). If small animals such as insects enter the external unit, a short circuit may be
caused near electrical components in the service panel.
• If the outdoor unit is installed at a level that is higher than the indoor unit, the water
that has condensed in the 3-way valve of the outdoor unit could travel to the indoor
unit. Therefore, use putty in the space between the pipe and the insulation to prevent
the entry of water to the indoor units.
Fig. A
Putty
6. HOW TO OPERATE DISPLAY UNIT
6.1. Display unit position
Never touch electrical components such as the terminal blocks except the button on
the display board. It may cause a serious accident such as electric shock.
• Once refrigerant charging is completed, be sure to open the valve prior to
performing the local settings. Otherwise, the compressor may fail.
• Discharge any static electricity from your body before touching the push buttons.
Never touch any terminal or pattern of any parts on the control board.
• The positions of the buttons on the outdoor unit control board are shown in the
following figure.
• Various settings can be adjusted by changing push buttons on the board of the outdoor
unit.
En-12
WARNING
Insulation material
Minimum thickness [in (mm)]
70%
75%
80%
or more
or more
or more
5/16 (8)
3/8 (10)
1/2 (13)
3/8 (9)
7/16 (11)
9/16 (14)
3/8 (10)
1/2 (12)
9/16 (15)
3/8 (10)
1/2 (12)
5/8 (16)
3/8 (10)
1/2 (13)
5/8 (16)
7/16 (11)
1/2 (13)
11/16 (17)
7/16 (11)
1/2 (13)
11/16 (17)
WARNING
Insulation
WARNING
CAUTION
85%
6.2. Description of display and buttons
or more
11/16 (17)
11/16 (18)
• The printed characters for the LED display are shown below.
3/4 (19)
13/16 (20)
13/16 (21)
LED display part
7/8 (22)
7/8 (22)
Button part
Display lamp
(1) POWER / MODE
(2) ERROR
(3) PUMP DOWN
(L1)
(4) LOW NOISE
(L2, L3)
(5) PEAK CUT
(L4, L5, L6)
Button
S134
MODE
S133
SELECT
S132
ENTER
S131
S130
PUMP DOWN
Function or operation method
Lights on while power on. Local setting in out-
Green
door unit or error code is displayed with blink.
Blinks during abnormal air conditioner
Red
operation.
Lights on during pump down operation.
Orange
Lights on during Low noise mode when local
setting is activated. (Lighting pattern of L2 and
Orange
L3 indicates low noise level)
*Refer to the page 13.
Lights on during Peak cut mode when local
setting is activated. (Lighting pattern of L4, L5
Orange
and L6 indicates peak cut level)
*Refer to the page 14.
Function or operation method
To switch between "Local setting" and "Error code
display".
To switch between the individual "Local settings"
and the "Error code displays".
To fix the individual "Local settings" and the "Error
code displays".
EXIT
To return to "Operation status displays."
To start the pump down operation.