Fujitsu AB A36LBT Series Ontwerp en technische handleiding - Pagina 24
Blader online of download pdf Ontwerp en technische handleiding voor {categorie_naam} Fujitsu AB A36LBT Series. Fujitsu AB A36LBT Series 48 pagina's. Ceiling type
11-2.
EXTERNAL OUTPUT
OPERATION STATUS OUTPUT
An air conditioner operation status signal can be output.
Circuit diagram example
z
Indoor
control PC board
Connector
24V DC
1
V
2
*10 m
* Make the distance from the PC board to the connected unit within 10m.
Relay spec. : Max.24VDC, 10mA to less than 500mA.
Operation
Indoor unit
Stop
ON
Output signal
OFF
Parts (Optional)
z
Model name
UTY-XWZX
Wire (External output)
Connected unit
Ex.)Relay unit
Signal
Field supply
- (01 - 21) -
Ex.)Display
Relay
power
supply