Fujitsu AG G12LVCB Series Ontwerp en technische handleiding - Pagina 49

Blader online of download pdf Ontwerp en technische handleiding voor {categorie_naam} Fujitsu AG G12LVCB Series. Fujitsu AG G12LVCB Series 49 pagina's. Floor type

Fujitsu AG G12LVCB Series Ontwerp en technische handleiding
10.

SAFETY DEVICES

Circuit protection
Fan motor protection
Compressor protection
Heater Protection
Protection form
Current fuse
(NEAR THE TERMINAL)
Current fuse
(MAIN PRINTED CIRCUIT
BOARD)
Thermal protection
program
Thermal protection
program
(DISCHARGE TEMP.)
Current fuse
Thermal protection switch
(Heater temp.)
- (02 - 15) -
Model
AOG09LVCN
AOG12LVCN
250V 20A
250V 5A
250V 15A
250V 3.15A
OFF : 100±15°C
ON : 95±10°C
OFF : 110°C
ON : After 7 minutes
250V 5A (2pcs)
OFF: 55
ON: 45
AOG14LVCN
250V 5A
250V 3.15A
250V 5A(1pc)
+3
°C
-3
+4
°C
-4