11-2.
EXTERNAL OUTPUT
OPERATION STATUS OUTPUT
An air conditioner operation status signal can be output.
Circuit diagram example
z
Indoor unit
control PC board
Connector
1
2
* Make the distance from the PC board to the connected unit within 10 m.
Operation
Indoor unit
Output signal
Parts (Optional)
z
Parts name
External connect kit
Ex.) Relay unit
DC 24 V
V
10 m*
Signal
Field supply
Stop
ON
OFF
Model name
UTY-XWZX
- (01 - 21) -
Connected unit
Ex.) Display
Relay
power
supply
Relay spec.:
Max.DC 24 V, 10 mA to less
than 500 mA.