Condensate drain pipe should be connected into special drain system for air
conditioner.
(4)
The drain pan has primary and secondary drain connection. Condensate removal
is performed by attaching a 3/4" PVC pipe to the evaporator coil pan and
terminated in accordance with local or state Plumbing/HVAC codes. The
installation must include a "P" style trap that is located closely to the evaporator
coil. Do not over-tighten the drain connection in order to prevent possible damage
to the evaporator drain pan. See the following figure for details of a typical
condensate line "P" trap.

4.5 Ductwork

This coil is designed for a complete supply and return ductwork system.
Do not operate the unit without all ductwork completed.
Do not operate this product without all ductwork attached.
Inadequate ductwork that restricts airflow can result in improper performance and
compressor or heater failure. Ductwork is to be constructed in a manner that limits
restrictions and maintains suitable air velocity. Ductwork is to be sealed to the unit in a
manner that will prevent leakage.
Return ductwork: Do not terminate the return ductwork in an area that can
introduce toxic or objectionable fumes/odors into the ductwork. The return ductwork is
to be introduced into the coil.
Return Air Filters: Each installation must include a return air filter. This filtering may
be performed at the coil or externally such as a return air filter grille.