Code Fault
Description
AF
Auxiliary fault
Indicates a shutdown initiated by pushing the emergency
input shutdown
stop switch. (TRES models only)
Not used on RES models.
HE
High engine
Shutdown occurs if the engine coolant temperature
temperature
exceeds the maximum temperature for more than
shutdown
5 seconds. This function becomes active after the engine
reaches the crank disconnect speed.
LOP
Low oil
Shutdown occurs if a low oil pressure condition exists for
pressure
more than 5 seconds. This function becomes active
shutdown
30 seconds after the engine has reached crank disconnect
speed (30 second inhibit).
Note: The low oil pressure shutdown does not protect
against low oil level. Check the oil level at the engine.
Overcrank
Shutdown occurs after 3 unsuccessful starting attempts.
OC
shutdown
The crank cycle is set for three starting attempts of 15
seconds cranking and 15 seconds rest.
Locked rotor
The generator set also shuts down on OC if no engine
rotation is sensed during cranking. Shuts down 3 seconds
after the fault is detected.
OF
Overfrequency
Shutdown occurs when the governed frequency exceeds
shutdown
110% of the system's frequency setpoint for more than 5
seconds. This function becomes active 10 seconds after
engine start (10 second inhibit).
OS
Overspeed
Shutdown occurs if the engine speed exceeds 110% of the
shutdown
normal running speed for more than 0.3 seconds.
OU
Overvoltage
Shutdown occurs if the voltage exceeds 120% of the
shutdown
system nominal voltage for more than 2 seconds.
UF
Underfrequency
Shutdown occurs if the governed frequency falls below
shutdown
54 Hz for more than 5 seconds.
Shutdown also occurs if the governed frequency falls below
56.5 Hz for more than 60 seconds.
This function becomes active 10 seconds after engine start.
(10 second inhibit).
UU
Undervoltage
Shutdown occurs if the voltage falls below 80% of the
shutdown
nominal system voltage for more than 10 seconds.
HB
High battery
Fault code is displayed if the engine starting battery voltage
voltage warning
rises above 16 VDC for more than 30 seconds when the
engine is running. Not operative during the engine crank
cycle, this fault condition does not inhibit engine starting.
The fault condition clears when the battery voltage returns
to an acceptable level.
LB
Low battery
Fault code is displayed if the engine starting battery voltage
voltage warning
falls below 11 VDC for more than 30 seconds when the
engine is not running. Not operative during the engine
crank cycle, this fault condition does not inhibit engine
starting.
The fault condition clears when the battery voltage returns
to an acceptable level.
Figure 2-5 ADC-RES Fault Codes
TP-6515 2/21
Check
Check the position of the emergency
stop button. (TRES models only)
Check for blocked air inlets and
exhaust outlets.
Check for leaks in the lubrication
system.
Check the oil level and add oil if the
level is low.
Check the fuel supply, spark plug,
and battery.
Check for loose connections.
Contact an authorized
distributor/dealer for service if
problem continues.
Contact an authorized
distributor/dealer for service if
problem continues.
Contact an authorized
distributor/dealer for service if
problem continues.
Contact an authorized
distributor/dealer for service if
problem continues.
Reduce the load and restart the
generator set.
Contact an authorized
distributor/dealer for service if
problem continues.
Reduce the load and restart the
generator set.
Contact an authorized
distributor/dealer for service if
problem continues.
Check the battery rating and
condition.
Check the battery charger operation.
Check the battery rating and
condition.
Check the battery charger operation.
Charge or replace the battery.