Kohler 14RESL Installatiehandleiding - Pagina 21

Blader online of download pdf Installatiehandleiding voor {categorie_naam} Kohler 14RESL. Kohler 14RESL 48 pagina's. Residential and light commercial generator sets
Ook voor Kohler 14RESL: Handleiding voor probleemoplossing (8 pagina's)

Kohler 14RESL Installatiehandleiding
1.7.2

Fuel Conversion, 20RES/RESL

For LP vapor fuel, an orifice is used in the fuel line. The
unit is typically shipped set up for natural gas, with the
loose orifice tied near the fuel solenoid valve. To convert
to LP vapor, install the orifice and disconnect the spark
advance leads as described below. See Figure 1-15 for
the fuel system component locations.
Procedure to Convert from NG to LP, 20RES/RESL
1. Press the OFF button on the generator set
controller and remove the F3 fuse (located in the
service access area).
2. Disconnect the power to the battery charger.
3. Disconnect the generator set engine starting
battery, negative (--) lead first.
4. Turn off the fuel supply.
5. Remove the hose clamp and fuel hose from the
hose fitting. See Figure 1-15.
6. Insert the orifice into the hose fitting.
Figure 1-15.
7. Slide the hose onto the hose fitting and secure it
with the clamp.
8. Disconnect digital spark-advance module (DSAI)
leads 65 and N5 for LP. The DSAI leads are located
near the fuel solenoid valve. See Figure 1-11 or
Figure 1-12.
9. Connect and turn on the new fuel supply.
10. Reconnect the generator set engine starting
battery leads, negative (--) lead last.
11. Reconnect power to the battery charger.
12. Reinstall fuse F3 and start the generator set by
pressing the RUN button on the generator set
controller.
TP-6733 8/11
Note: LP setup
shown
1. LP orifice
2. Hose fitting
3. Regulator
4. Fuel inlet, 1/2 in. NPT female
5. Vent hose
See
Figure 1-15 Fuel Regulator and LP Orifice,
20RES/RESL
13. Check for leaks using a gas leak detector.
14. Run the generator set and check the operation.
Use the controller to adjust the output and stability if
necessary. See Section 1.15 for instructions.
15. Press the OFF button to shut down the generator
set.
Conversion from LP to Natural Gas
To convert from LP vapor to natural gas, remove the fuel
orifice and connect the DSAI leads together.
Fuel
Natural Gas
LP
Figure 1-16 DSAI Connections
2
1
3
4
5
DSAI Leads 65 and N
Connect lead 65 to N
Disconnect
Section 1 Installation
GM66563
21