Troubleshooting
Replace AVR
Unit
Main Winding
White-Black
Field Winding
Between slip ring
Exciter Winding
DC Winding
Orange-Orange
Brush
NOTE: Alternator should not be in contact with panel, AVR, etc during above resistance tests. Alternator should be
tested at room temperature.
8
Item
GEN 5.0
Red-Blue
0.37Ω±10%
0.37Ω±10%
47.9Ω±10%
Blue-Blue
1.30Ω±10%
-
Length
With engine stopped, replace AVR with a
new AVR. Start engine and adjust trimmer
on back of AVR. Test terminal voltage.
Voltage should be between 95-135V. If
voltage is met, original AVR is not adjusted
properly or faulty. Replace as necessary. If
voltage not met, check circuit breakers and
receptacles.
Generator Spec.
PRO5.2/5.2E
0.27Ω±10%
0.27Ω±10%
46.6Ω±10%
1.60Ω±10%
0.10Ω±10%
9mm
KohlerPower.com
REMARK
PRO7.5/7.5E
0.13Ω±10%
Red-White
(PRO 7.5 E)
0.13Ω±10%
56.4Ω±10%
1.02Ω±10%
0.08Ω±10%
Service limit:
5mm
37 690 01 Rev. --