Replacing Protective Fuses
NOTE: Comply with technical specifications for
fuses. Using wrong fuse may cause
damage to generator.
Replace fuses (J) in event of failures due to
overcurrents. Before replacing worn fuses
(J) with new ones, always contact a Kohler
portable dealer to determine cause of failure
and overcurrent.
1. Turn MODYS (B) key to OFF position.
Generator stops.
2. Unscrew 12V fuse holder for MODYS (B)
and lighting and 240V fuse holder for
MODYS (B) and working hours counter.
3. Visually check condition of both fuses (J).
4. Replace worn fuse(s) (J) with a new one of
5x20 type, rating 2A.
5. Screw two fuse holders back in.
Transporting Generator
Before transporting generator, check that bolts
are correctly tightened, close fuel valve (P)
and disconnect battery. Generator should be
transported in its normal operating position;
never lay it on its side. Ensure where generator
is to be stored or used is carefully prepared
beforehand.
Repairing Minor Faults - MODYS Alarms and Faults
Color of
Pictograms
LED
Red
Red
Red
Red
Red
Flashing
Red
34 590 01 Rev. A
Type of Fault
Engine
temperature
Battery or
Problem with alternator
charging
alternator
Oil pressure or
Shutdown: incorrect oil
low oil level
pressure or low oil level
Non-starting fault
Overspeed
Speed too low
KohlerPower.com
Repairs/Service Parts
We recommend that you use a Kohler portable
dealer for all maintenance, service, and
replacement parts for engine. To find a Kohler
portable dealer visit KohlerPower.com or call
1-800-544-2444 (U.S. and Canada).
Storage
Long-term storage of your generator will require
some preventative procedures to guard against
deterioration.
NOTE: Do not connect with any electrical
devices (unloaded operation).
If engine will be out of service for 2 months or
more follow procedure below.
1. Add Kohler PRO Series fuel treatment or
equivalent to fuel tank. Run engine 2-3
minutes to get stabilized fuel into fuel system
(failures due to untreated fuel are not
warrantable).
2. Change oil while engine is still warm from
operation. Remove spark plug(s) (X) and
pour about 1 oz. of engine oil into cylinder(s).
Replace spark plug(s) (X) and crank engine
slowly to distribute oil.
3. Clean generator.
4. Store generator in a dry, well-ventilated
place, with cover placed over it. When
covering generator, be sure to do so only
after engine and muffler/shield have
completely cooled down. Generator must
remain in same position as normal operation.
Issue
Shutdown: abnormal
engine temperature
charge output or weak
battery
3 consecutive
unsuccessful starting
attempts
Shutdown: generator
rotation speed
excessive
Shutdown: insufficient
generator rotation
speed
Possible Solution
Allow generator to cool
down and check air
cleaner and vents on
enclosure.
Contact a Kohler
portable dealer.
Allow generator to cool
down, top up and check
oil level.
Check that generator has
been started according to
recommendations in this
manual.
Contact a Kohler
portable dealer.
Contact a Kohler
portable dealer.