TROUBLESHOOTING
Disconnect the main power supply before any intervention to the unit. If you are not sure of the correct steps,
do not attempt to perform any repairs, and call a professional service!
Description
44 – Fan error
45 – Mandatory
maintenance/filter
clogged
46 – Heater
malfunction
47 - malfunction in
external temperature
sensor (45,46)
48 – Outlet temperature
sensor malfunction
(49,50)
49 – Inlet temperature
sensor malfunction
(51,52)
60 – Exchanger's
return sensor
malfunction (53,54)
61 – Room temperature
sensor malfunction
(55,56)
62 - malfunction in
external temperature
sensor from BMS
63 - malfunction in room
temperature sensor
from BMS
79 – Heating reduced
due to low air flow
65 – Communication
error
Unit's not working
The heating switches
off automatically
11
Unit
Likely problem
behaviour
Unit
Overheated fan or non fuctional
out of order
motor
Unit
Filter clogged or the time to replace
operational
it has come
Unit
Heater malfunction
out of order
Unit
Temperature sensor malfunction on
out of order
terminals 45,46
Unit
Temperature sensor malfunction on
out of order
terminals 49,50
Unit
Temperature sensor malfunction on
out of order
terminals 51,52
Unit
Temperature sensor malfunction on
out of order
terminals 53,54
Unit
Temperature sensor malfunction on
out of order
terminals 55,56
Limited
Temperature sensor malfunction in
operation of
BMS
the device
Limited
Temperature sensor malfunction in
operation of
BMS
the device
Unit
Only information
operational
Unit out of
Communication error
order
Unit
Power supply interrupted
out of order
Cracked fuse
Unit
The heater overheats
operational
but not
heating
2VV. Creating innovative solutions for you and your business since 1995.
Solution
Determine the cause of the overheating (defective
bearing, short-circuit...) or replace the motor.
Replace filters. After replacing, do not forget to reset the
MENU 1616 – FILTER TIMER
Check the heater and the condition of the safety
thermostat Does the heater have proper cooling?
Check engine running.
Check that the sensor is correctly connected to the
electronics or test it measuring its resistance (the
resistance value at +20°C is around 10kW)
Check that the sensor is correctly connected to the
electronics or test it measuring its resistance (the
resistance value at +20°C is around 10kW)
Check that the sensor is correctly connected to the
electronics or test it measuring its resistance (the
resistance value at +20°C is around 10kW)
Check that the sensor is correctly connected to the
electronics or test it measuring its resistance (the
resistance value at +20°C is around 10kW)
Check that the sensor is correctly connected to the
electronics or test it measuring its resistance (the
resistance value at +20°C is around 10kW)
Check that in the BMS that the address where the
sensors sends the data is properly set
(on the right regulator) Check the function of the sensor
in the BMS
Check that in the BMS that the address where the
sensors sends the data is properly set
(on the right regulator) Check the function of the sensor
in the BMS
The air flow settings were reduced, limiting the heater
output to prevent overheating
Check the communication cable for damages and if it
is properly connected Observe the wiring diagram to
prevent occurrences that may disrupt communication
(wiring near high tension, phenomena on site causing
disruptions)
Check that the power supply is not interrupted
Check the fuse in side the control module
The heater overheats due to insufficient air flow. Check
that the ventilators are in good order and that the air
supply is not disrupted.