CALIBRATION (continued)
3. Calibration Procedure
continued...
The Calibrate button will turn green and the
red text will disappear when the conditions
required for calibration have been met
(Fig. 13).
When ready, press the Calibrate button and
the screen will indicate that the calibration
was successful (Fig. 14). Press BACK to
return to the prior screen; Re-Calibrate if
something occurred which made the
Figure 13 - CAL READY
calibration suspect, or OK, after which the
indicator will very briefly flash a Calibration
Successful screen, and then progress to the
Display Screen.
Remove the weight and observe the output.
It should read 0 VDC or 4 mA with nothing
touching the tension sensing roller. If these
conditions are satisfied, calibration is now
complete.
Figure 14 - CALIBRATION SUCCESSFUL
7