Dimming Channel 2 functions (factory default in brackets):
4.1
Light level
4.2
Presence detection
4.3
Absence detection
4.4
Switch level on (9)
4.5
Switch level off (9)
4.6
Memorise (N)
4.7
On value (99)
4.8
Off value (0)
4.9
Fade value (10)
4.10 Fade mins (0)
4.11 Max value (99)
4.12 Min value (1)
4.13 Speed on (40)
4.14 Speed set (5)
4.15 Set seconds (120)
4.16 Burn-in (0)
5
User Menu
DD-LCDHS user menu or UHS handset functions:
5.1
Lux up
5.2
Lux down
5.3
Scene up
5.4
Scene down
5.5
Scene#
5.6
Override on
5.7
Override off
5.8
Cancel
5.9
Set
Maintained illuminance level (adjustable between 1 and 999). At 999 the
output will be always be at maximum.
Not used. See Channel 1 setting.
Not used. See Channel 1 setting.
Not used. See Channel 1 setting.
Not used. See Channel 1 setting.
If this is set to Yes, the last manual lux level set will be memorised and
used as the new switch on level.
Dimming output level when switched on (0-99).
Dimming output level when switched off (0-99). If a non-zero off value is
set, then the output will toggle between this value and completely off
depending on the switch level on and off values. For example, if it is light
outside, the fittings will be off if there is no occupancy. If it is dark outside,
they will adopt the preset off value. This feature is only enabled if ‗Min
value' is set to 99.
After occupancy ceases, this dimming output level is loaded for the fade
time (adjustable between 0 and 99).
This is the time period (adjustable between 0 and 99 minutes) that the
luminaire will be held at the fade value before turning off. A value of 0
disables the fade function.
Maximum dimming output level (adjustable between 0 and 99).
Minimum dimming output level (adjustable between 0 and 99).
Determines the dimming response speed after the setup time has
finished. Measured in 0.1 sec intervals.
Determines the dimming response speed during the set up time.
Measured in 0.1 sec intervals. If set to 0 will disable dimming for ―Set
seconds‖ below, used if fittings are required to warm up before dimming.
Determines how long the dimming response set-up period lasts on power-
up or on setting change (adjustable between 1 and 999 seconds). This
enables the desired lux level to be achieved rapidly when the lights come
on, or during setup.
Determines how long the output will be at 100% so that lamps ‗burn-
in' (adjustable between 1 and 999 hours). The 'burn-in' time is not affected
by power supply interruptions. To disable burn-in set to 0.
Increase light level. Reverts when occupancy cycle complete.
Decrease light level. Reverts when occupancy cycle complete.
Steps up between 6 pre-defined scenes.
Steps down between 6 pre-defined scenes.
Select the individual scene, between 0 and 6. (1 = min. output; 2 = 10%;
3 = 25%; 4 = 50%; 5 = 75%; 6 = 100%)
Permanently overrides the luminaire output on.
Permanently overrides the luminaire output off.
Cancels the on or off override, returning the detector to normal operation.
If sent before using lux up or lux down, it will set the light level as in 4.1
page 7