Detection diagram
Range
Note: illustration shows an average of the walk across and walk towards figures below.
Walk across
Wiring diagram
Power-up test procedure
When power is applied to the unit, the load will turn on immediately.
For the first 5 minutes of operation the time out period is 10 seconds to aid commissioning.
Vacate the room or remain very still for more than 10 seconds and wait for the load to switch off.
Check that the load switches on when movement is detected.
When the 5 minutes have elapsed the time out will be 10 minutes.
Fault finding
What if the load does not turn ON?
Check that the live supply to the circuit is good.
Check that the load is functioning by bypassing the sensor (e.g. link L and L/ Out).
What if the load does not turn OFF?
Ensure that the area is left unoccupied for longer than the 10 minute time out period.
Ensure that the sensor is not adjacent to circulating air, heaters or lamps.
2
Height
Range Diameter
7m
16m
2.8m
9m
Walk towards
Height
Range Diameter
7m
10m
2.8m
5m