Aqua PRO PRO400 Gebruiksaanwijzing - Pagina 4
Blader online of download pdf Gebruiksaanwijzing voor {categorie_naam} Aqua PRO PRO400. Aqua PRO PRO400 13 pagina's. Heat pump pool & spa heater
Operating Instructions
Condensation
All heat pump pool heaters will have
condensation. It is typical to have as
much as 6-8 gallons of condensation or
water per hour, during a warm, humid
day. Do not mistake this for a leak.
If you are not sure the water is a leak or
is condensation, there are two ways to
check this. First, use a pool test strip to
see if there is any chlorine or bromine
in the water. If there is, contact the
factory for service. Second, you can turn
off the heater, leave the filter pump
running and see if the water stops. If
you do not see additional water, then
the original water was condensation.
Pool Blankets
A pool blanket has been proven to
greatly reduce the heat loss in the pool
and will save as much as 50% - 60% in
your heating bills. During the start of
the swimming season and the end of
the season, if a pool blanket is not
used, the heater may not be able to
maintain your desired temperature
without the use of the blanket.
Seasonal Shutdowns
At the end of your swimming season
you may have freezing weather
conditions. The unions (NOT provided)
must be disconnected to drain any
water in the pipes. Failure to do so may
cause the heat exchanger to expand
and crack. This will void your warranty.
If you live in an area that does not have
freezing weather conditions but are
subject to extended periods of non-use,
allow the filtration system to continue
to run water through the heater. Or
you can drain the unit of all water.
Pool Openings
If at the end of the previous season you
disconnected the unions, be sure to
connect them before you turn on the
filtration system. Once the pool has
been cleaned and the unit has been
checked for leaks, turn the power on
the heater and set the thermostat to
the desired temperature.
Note: It may take up to three days to
reach the desired temperature during
the opening of the swimming season.
Without a pool blanket, it may take
even longer and may not reach the
desired temperature until later in the
season.
www.aquaprosystems.com
Weather Conditions
Weather conditions play a big part in
the operation of the heater. Low
outside ambient temperature, high
winds, low relative humidity, and a
large amount of shading on the pool
will all have an effect on how much
time it takes to heat the pool and how
much time it might need to maintain
the desired temperature. Once the
outside ambient temperature drops
below 50ºF, the heater may not
operate.
Troubleshooting
Guide
If the heater is not operating during
the initial start-up, check to see if it has
been installed properly, per this
owner's manual. Make sure the breaker
has been sized properly. The following
are conditions to check before calling
Aqua Pro Systems for a service:
Unit is not running:
•
Check the power light. Check to see
if the breaker is set.
•
Make sure the filtration system is on
•
Make sure the thermostat is higher
than the pool water temperature
•
Make sure the filter is clean and is
allowing enough water to flow
•
Make sure the outside ambient
temperature is higher than 50ºF
•
Make sure the 5-minute time delay
has passed
Unit is running but not heating:
•
Check the air coming out of the top
of the unit. It should be
approximately 8ºF - 15ºF lower than
the surrounding ambient air
temperature. If not, call the factory
for service.
4
Unit runs continuously:
•
Check for correct wiring.
•
Lower the desired water
temperature below the pool water
temperature. If the unit is still
running, call the factory for service.
•
If the unit shuts off when the
thermostat is lowered, it may be
running continuously because it
cannot reach the desired
temperature. A pool blanket may
be required to help reach this
temperature. Also, the filter pump
may need to run longer for the
heater to reach the desired
temperature.
Unit is cycling:
•
Check the filters for proper water
flow.
•
Check the evaporator coil for severe
frost.
•
Unit could be low on refrigerant.
At this point, call the factory for
service and turn off the power to
the heater to keep the cycling from
damaging the compressor.