Avtech TMP-SDT-SEN Installatie Opmerking - Pagina 3
Blader online of download pdf Installatie Opmerking voor {categorie_naam} Avtech TMP-SDT-SEN. Avtech TMP-SDT-SEN 5 pagina's. Difgital temperature & analog sensor
Digital Temperature & Analog Sensor (RMA-DTA-SEN)
1. Scroll down to your external digital sensor(s), the total number of which will vary
depending on the Room Alert model.
2. Find the digital sensor interface that matches the port you connected your Digital
Temperature & Analog Sensor to.
3. Notice that your Room Alert automatically detects your sensor and inserts a drop-down
list in "Sensor Type," which defaults to "Temp/Humidity." Select "Temp/Analog" to
bring up the interface for your Digital Temperature & Analog Sensor.
4. Then, using the set of fields on the right, configure your Temperature & Analog Sensor
to calculate your analog sensor's output signal to scale. In this example, we are
converting volts to amperage:
• Click "Enable" to turn on the "Reference," "Scale" and "Units" fields.
• In "Reference," enter values from 5 to 0 that represent the "High" and "Low"
points of your analog sensor's output signal range. Here, we've left the default
values of 5 to 0.
• In "Scale," enter the "High" and "Low" points of the scale you want the
"Reference" reading to be converted to. In this example, we would like to convert
0-5 volts to 0-20 amps, so we've put "20" in "High" with "0" in "Low."
AVTECH Software, Inc.
Page 3 of 5
AVTECH.com