Particulate and gaseous contamination specifications

This section defines the limitations that help avoid any equipment damage or failure from particulate and gaseous contamination.
If the levels of particulate or gaseous pollution exceed the specified limitations and result in equipment damage or failure, you
may need to rectify the environmental conditions. Remediation of environmental conditions is the responsibility of the customer.
The following table describes the particulate contamination specifications:
Particulate contamination
Air filtration
Conductive dust
Corrosive dust
The following table describes the gaseous contamination specifications:
Gaseous contamination
Copper coupon corrosion rate
Silver coupon corrosion rate
NOTE:
Maximum corrosive contaminant levels measured at ≤50% relative humidity.
26
Technical specifications
Heatsink
Two 1U high performance
heat sink
Processor/DIMM
DIMM
blank
blanks
Not required
Not
required
Specifications
Data center air filtration as defined by ISO Class 8 per ISO
14644-1 with a 95% upper confidence limit.
NOTE:
This condition applies only to data center
environments. Air filtration requirements do not apply to
IT equipment designed to be used outside a data center, in
environments such as an office or factory floor.
NOTE:
Air entering the data center must have MERV11 or
MERV13 filtration.
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
NOTE:
This condition applies to data center and non-data
center environments.
● Air must be free of corrosive dust.
● Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
NOTE:
This condition applies to data center and non-data
center environments.
Specifications
<300 Å/month per Class G1 as defined by ANSI/
ISA71.04-1985.
<200 Å/month as defined by AHSRAE TC9.9.