ensto AVR400 SDIM Bedieningshandleiding - Pagina 7

Blader online of download pdf Bedieningshandleiding voor {categorie_naam} ensto AVR400 SDIM. ensto AVR400 SDIM 9 pagina's.

ensto AVR400 SDIM Bedieningshandleiding

Recommended installation heights

0
5
Ceiling mounted detection pattern (m)
DIP Switch Settings
Detection Area
Sensor sensitivity can be adjusted by selecting the combi-
nation on the DIP switches to fit precisely for each specific
application. Note: by choosing "Sensor OFF", it becomes
an ordinary driver without occupancy detection.
1
2
100%
75%
50%
Sensor OFF
Daylight
Set the level according to the fixture and environment.
The light will not turn on if ambient lux level exceeds the
daylight threshold preset.
5
6
Disabl e
50Lux
10Lux
5Lux
Stand-by Dimming Level
The setting is used to select the desired dimmed light level
used in periods of absence for enhanced comfort and safety.
9
I
10%
II
30%
4
10%
30%
50%
75%
I – 100%
II – 75 %
III – 50%
IV – Sensor OF F
I – Disable
II – 50Lux
III – 10Lux
IV – 5 Lu x
I – 10 %
II – 30%
PEM2201 / 23.04.2021
4
Wall mounted detection pattern (m)
Hold Time
Select the DIP switch conguration for the light on-time
after presence detection. This function is disabled when
natural light is sufficient. Note: this function is disabled
when the natural daylight exceeds the daylight threshold
IV setting for more than 5 minutes.
3
4
I
5s
II
30s
II I
3min
IV
10min
Stand-by Period
This is the time period you would like to keep at the low
light output level before it is completely switched off in
the long absence of people. Note: "0s" means on/off con-
trol; "+∞" means the stand-by period is infinite and the
light is effectively controlled by the daylight sensor, off
when natural light is sufficient and automatically on at
dimming level when insufficient.
7
8
I
0s
II
10s
III
30min
+
IV
9
10%
30%
50%
75%
I – 5s
II – 30s
III – 3min
IV – 10min
I – 0 s
II – 10s
III – 30min
IV – +
7 / 9