Dell EMC S4112-ON Series Installatiehandleiding - Pagina 8

Blader online of download pdf Installatiehandleiding voor {categorie_naam} Dell EMC S4112-ON Series. Dell EMC S4112-ON Series 26 pagina's.

Dell EMC S4112-ON Series Installatiehandleiding
Environmental—switch location—continuous temperature range is from 5° to 40°C
(50° to 104°F).
Operating humidity is from 5 to 85 percent non-condensing, continuous.
In a dry, clean, well-ventilated, and temperature-controlled room, away from heat
sources such as hot cooling vents or direct sunlight.
Away from sources of severe electromagnetic noise.
Positioned in a rack or cabinet, or on a desktop with adequate space in the front, back,
and sides for proper ventilation and access.
Install the switch in Information Technology Rooms in accordance with Article 645 of
the National Electrical Code and NFPA 75.
For more information about switch storage and environmental temperatures, see
Specifications.

Cabinet placement

Install the S4112-ON Series switch only in indoor cabinets designed for use in a controlled
environment.
Do not install the S4112-ON Series switch in outside cabinets. For cabinet placement
requirements, see
The cabinet must meet minimum size requirements. Airflow must be in accordance with the
Electronic Industries Alliance (EIA) standard. Ensure that there is a minimum of 5 inches
(12.7 cm) between the intake and exhaust vents and the cabinet wall.

Rack mounting

When you prepare your equipment rack, ensure that the rack is grounded. Ground the
equipment rack to the same ground point the power service in your area uses. The ground
path must be permanent.

Switch ground

Dell EMC recommends grounding your switch. Use the S4112-ON Series switch in a CBN.
For more information, see
8
Site preparations
Site
selection.
Ground
cable.