Dell Networking S5000 Installatiehandleiding - Pagina 43

Blader online of download pdf Installatiehandleiding voor {categorie_naam} Dell Networking S5000. Dell Networking S5000 50 pagina's. Data center switch
Ook voor Dell Networking S5000: Configuratiehandleiding (12 pagina's), Configuratiehandleiding (17 pagina's), Aan de slag handleiding (37 pagina's)

Dell Networking S5000 Installatiehandleiding

Technical Specifications

NOTE: Operate the product at an ambient temperature not higher than 40°C.
CAUTION: Lithium Battery Caution: There is a danger of explosion if the battery is incorrectly replaced.
NOTE: Replace the battery only with same or equivalent type. Dispose of the batteries according to the
manufacturer's instructions.
Table 5. Chassis Physical Design
Parameter
Height
Width
Depth
Chassis weight with factory-installed components
Rack clearance required
Table 6. Environmental Parameters
Parameter
Operating temperature
Operating humidity
Storage temperature
Storage humidity
Relative humidity
Maximum thermal output
Maximum Altitude
Table 7. Power Requirements
Parameter
AC Power supply
DC Power supply
Maximum current draw per system
Maximum power consumption
Specifications
1.71 inches (43.5 mm)
17.4 inches (441 mm)
28 inches (711 mm)
34 pounds (approx.) (15.42 kg)
Front: 5 inches (12.7 cm)
Rear: 5 inches (12.7 cm)
Specifications
32° to 104°F (0° to 40°C)
10 to 85 percent (RH), noncondensing
–40° to 158°F (–40° to 70°C)
5 to 95 percent (RH), noncondensing
10 to 85 percent, noncondensing
2388 BTU/hr
No performance degradation to 6600 ft
Specifications
100 VAC ~ 240 VAC 50/60 Hz
–48V ~ –60V VDC
7 A @ 100 VAC
3.5 A @ 200 VAC
700 Watts
7
43