Miele PG 8055 Installatieplan - Pagina 6

Blader online of download pdf Installatieplan voor {categorie_naam} Miele PG 8055. Miele PG 8055 45 pagina's.

Miele PG 8055 Installatieplan
4. Voltage (standard version)
It is always recommended to make electrical connection via a
plug and socket so that electrical safety checks, e.g. during
repair or service work, can be carried out easily. The socket
must be accessible after machine installation. A fixed
electrical connection is possible via an on-site main switch
providing complete isolation from the mains for all poles. The
contact gap must be at least 3 mm. In order to increase
safety, the installation of an earth leakage circuit breaker is
recommended. If necessary, equipotential bonding with good
galvanic contact must be guaranteed in compliance with all
applicable local and national installation codes.
Protection class IP 21
Cold or hot water
Maximum temperature
Max. water hardness
Minimum flow pressure
Minimum flow pressure with extended water intake
Maximum pressure
Flow rate
On-site threaded union in accordance with DIN 44991 (flat
sealing)
Length of connection hose (included)
A double check valve must be fitted when installed in GB.
Waste water
Drain hoses (int. dia. x wall thickness)
Length of drain hose - Machine
Max. drain hose extension
Max. drain pump head height from base of machine
Max. transient flow rate
On-site hose sleeve for drain hose (outer dia. x length)
External
Connection of 1 dispenser for liquid detergent on rear of
dispensing
machine
(optional)
Machine feet
Height-adjustable
Machine foot diameter
Machine foot socket
Installation PG 8055
23.09.2016
Connected load
Fuse rating
Connection cable, min. gauge
Connection cable length (H05(07)RN-F) without
plug
Voltage (standard version)
Connected load
Fuse rating
Connection cable, min. gauge
Length of connection cable (H05(07)RN-F) with
plug
Voltage
Connected load
Fuse rating
Connection cable, min. gauge
Length of connection cable (H05(07)RN-F) with
plug
V/Hz
3N AC 400/50
kW
8.9
A
3 x 15-16
mm²
5 x 2.5
m
Approx. 2.1
V/Hz
AC 230/50
kW
5.9
A
30-32
mm²
3 x 4
m
Approx. 2.1
V/Hz
AC 230/50
kW
3.4
A
13-16
mm²
3 x 1.5
m
Approx. 2.1
°C
65
°dH
60
kPa
200
kPa
40
kPa
1,000
l/min
7.5
Inch
3/4" male thread
m
Approx. 1.7
mm
22 x 6
m
Approx. 1.5
m
Approx. 4.0
m
1.0
l/min
16
mm
22 x 30
mm
-0/+60
mm
35
M
8
6