Allmess ITRON EquaScan pMIURF Montage- en programmeerinstructies - Pagina 5
Blader online of download pdf Montage- en programmeerinstructies voor {categorie_naam} Allmess ITRON EquaScan pMIURF. Allmess ITRON EquaScan pMIURF 8 pagina's. Pulse meter radio module
ASSEMBLY AND PROGRAMMING INSTRUCTIONS
EquaScan pMIU
Pulse Meter radio module
SCOPE OF DELIVERY
• Pulse Meter RF communication module
• Assembly instructions
• 5 "Scotch Lock" type connectors for signal cable diameter 1,52
• 1 user plastic seal
• 1 screw 3,5x20 for wire cover
GENERAL INFORMATION
The EquaScan pMIU
serves to integrate pulse emitting meters into the Itron EquaScan radio system for mobile and fixed
RF
network data collection.
The module can be assembled, installed and integrated into the system of existing EquaScan radio meters in a few simple
steps. The EquaScan pMIU
software.
NOTE ON DISPOSAL
Used electronic devices and their batteries must not disposes of with normal household waste. We take all our products
back after use, free of charge, and disposed of them accordingly. Radio modules include a lithium Battery.
Do not incinerate, do not try to disassemble the module.Do not expose to temperature beyond the specifications.
PRE-INSTALLATION PRECAUTIONS
Prior the installation of the EquaScan pMIU
Where electronic devices are to be utilized, caution should be exercised to ensure that the EquaScan pMIU
in close proximity to power supply cables or strong electromagnetic sources such as electric motors or pumps.
Do not install the EquaScan pMIU
Characteristics
Operating ambient temperature
Storage temperature
Transport temperature
Protection Class
Battery lifetime
Signalparameters
RF
can be programmed quickly via the computer using an Itron inductive head and the EquaScan
RF
, check if the meter is equipped with a pulse output.
RF
on hot water piping, close to any source of heat, or exposed direct to the sunlight.
RF
Between 0°C and +55°C
Min. operating ambient temperature: -10°C to 5°C
(< 15 days/year)
Max. operating ambient temperature: 65°C (< 15days/year)
+5°C to +35°C < 1 year
Between -20°C and 70°C < 24 hours continuous Temperature
variation max. ±20°C/hour
IP68
12 years (+ 1 year reserve)
Max. Input Voltage
Max. Input Ampere
Max. Pulsfrequency
Min. pulse length ("Closed")
Min- pulse pause ("Open")
is not installed
RF
U
= 5V
max
I
= 5mA
max
f
≤ 17Hz
max
tc
≥ 6ms
min
to
≥ 50ms
min